Fault tracing
215
0050
ENCODER 1 CABLE
(0x7389)
Programmable fault:
Encoder 1 cable fault detected.
Check cable between FEN-xx interface and
encoder 1. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
0051
ENCODER 2 CABLE
(0x738A)
Programmable fault:
Encoder 2 cable fault detected.
Check cable between FEN-xx interface and
encoder 2. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
0052
D2D CONFIG
(0x7583)
Configuration of the drive-to-
drive link has failed for a reason
other than those indicated by
alarm
, for example start
inhibition is requested but not
granted.
Contact your local ABB representative.
0053
D2D COMM
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
and
) on the drive-to-
drive link are powered, properly connected to
the link, and have the correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new reference
1 and/or 2 for five consecutive
reference handling cycles.
Check the settings of parameters
and
on the master
drive.
Check the drive-to-drive link wiring.
0054
D2D BUF OVLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
0055
TECH LIB
(0x6382)
Resettable fault generated by a
technology library.
Refer to the documentation of the technology
library.
0056
TECH LIB CRITICAL
(0x6382)
Permanent fault generated by a
technology library.
Refer to the documentation of the technology
library.
0057
FORCED TRIP
(0xFF90)
Generic Drive Communication
Profile trip command.
Check PLC status.
0058
FIELDBUS PAR ERROR
(0x6320)
The drive does not have a
functionality requested by PLC,
or requested functionality has
not been activated.
Check PLC programming.
Check fieldbus parameter settings. See
parameter group
on page
0061
SPEED FEEDBACK
(0x8480)
No speed feedback is received.
Check the settings of the parameters in group
Check encoder installation. See the
description of fault
(ENCODER1) for
more information.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......