Parameter data
189
Parameter groups 10…99
Index
Parameter
Type
Range
Unit
FbEq
Update
time
Data
len.
Def
PT
Save
PF
Page
no.
10
START/STOP
10.01 EXT1 START FUNC
enum
0…6
-
-
2 ms
16
1
WPD
10.02 EXT1 START IN1
Bit pointer
-
2 ms
32
P.02.01.00 WPD
10.03 EXT1 START IN2
Bit pointer
-
2 ms
32
C.False
WPD
10.04 EXT2 START FUNC
enum
0…6
-
-
2 ms
16
1
WPD
10.05 EXT2 START IN1
Bit pointer
-
2 ms
32
P.02.01.00 WPD
10.06 EXT2 START IN2
Bit pointer
-
2 ms
32
C.False
WPD
10.07 JOG1 START
Bit pointer
-
2 ms
32
C.False
WPD
10.08 FAULT RESET SEL
Bit pointer
-
2 ms
32
P.02.01.02
10.09 RUN ENABLE
Bit pointer
-
2 ms
32
C.True
WPD
10.10 EM STOP OFF3
Bit pointer
-
2 ms
32
C.True
WPD
10.11 EM STOP OFF1
Bit pointer
-
2 ms
32
C.True
WPD
10.12 START INHIBIT
enum
0…1
-
1 = 1
2 ms
16
0
10.13 FB CW USED
Val pointer
-
2 ms
32
P.02.12
WPD
10.14 JOG2 START
Bit pointer
-
2 ms
32
C.False
WPD
10.15 JOG ENABLE
Bit pointer
-
2 ms
32
C.False
WPD
10.16 D2D CW USED
Val pointer
-
2 ms
32
P.02.17
WPD
10.17 START ENABLE
Bit pointer
-
2 ms
32
C.True
WPD
11
START/STOP MODE
11.01 START MODE
enum
0…2
-
1 = 1
-
16
1
WPD
11.02 DC MAGN TIME
UINT32
0…10000
ms
1 = 1
-
16
500
WPD
11.03 STOP MODE
enum
1…2
-
1 = 1
2 ms
16
2
11.04 DC HOLD SPEED
REAL
0…1000
rpm
1 = 10
2 ms
16
5
11.05 DC HOLD CUR REF
UINT32
0…100
%
1 = 1
2 ms
16
30
11.06 DC HOLD
enum
0…1
-
1 = 1
2 ms
16
0
11.07 AUTOPHASING
MODE
enum
0…2
-
1 = 1
-
16
1
12
DIGITAL IO
12.01 DIO1 CONF
enum
0…1
-
1 = 1
10 ms
16
0
12.02 DIO2 CONF
enum
0…2
-
1 = 1
10 ms
16
0
12.03 DIO3 CONF
enum
0…3
-
1 = 1
10 ms
16
0
12.04 DIO1 OUT PTR
Bit pointer
-
10 ms
32
P.06.02.02
12.05 DIO2 OUT PTR
Bit pointer
-
10 ms
32
P.06.02.03
12.06 DIO3 OUT PTR
Bit pointer
-
10 ms
32
P.06.01.10
12.07 DIO3 F OUT PTR
Val pointer
-
10 ms
32
P.01.01
12.08 DIO3 F MAX
REAL
3…32768
Hz
1 = 1
10 ms
16
1000
12.09 DIO3 F MIN
REAL
3…32768
Hz
1 = 1
10 ms
16
3
12.10 DIO3 F MAX SCALE
REAL
0…32768
-
1 = 1
10 ms
16
1500
12.11 DIO3 F MIN SCALE
REAL
0…32768
-
1 = 1
10 ms
16
0
12.12 RO1 OUT PTR
Bit pointer
-
10 ms
32
P.03.15.00
12.13 DI INVERT MASK
UINT32
0…63
-
1 = 1
10 ms
16
0
12.14 DIO2 F MAX
REAL
3…32768
Hz
1 = 1
10 ms
16
1000
12.15 DIO2 F MIN
REAL
3…32768
Hz
1 = 1
10 ms
16
3
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......