Bit pointer: Group, index and bit
10.03
EXT1 START IN2
(see above)
Selects the source 2 for the start and stop commands in external control location EXT1. See
parameter
selection
Note:
This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.04
EXT2 START FUNC
(see above)
Selects the source for the start and stop control in external control location EXT2.
Note:
This parameter cannot be changed while the drive is running.
(0)
NOT SEL
No source selected.
(1)
IN1
Source of the start and stop commands are selected by parameter
. The start/stop is controlled as follows:
(2)
3-WIRE
Source of the start and stop commands are selected by parameters
and
. The start/stop is
controlled as follows:
(3)
FBA
Start and stop control from the source selected by parameter
.
(4)
D2D
Start and stop control from another drive via D2D Control Word.
(5)
IN1F IN2R
The source selected by
is the forward start
signal, the source selected by
is the reverse
start signal.
(6)
IN1S IN2DIR
The source selected by
is the start signal
(0 = stop, 1 = start), the source selected by
the direction signal (0 = forward, 1 = reverse).
Par.
Command
0 -> 1
Start
1 -> 0
Stop
Par.
Command
0 -> 1
1
Start
Any
1 -> 0
Stop
Any
0
Stop
Par.
Command
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......