background image

AF(S)190, AF(S)205

Circuit Breaker A

T5N400

T5S400

T5H400 T5L400

T5V400

Fuse A/Class

400/RK5

400J

Max Short Circuit Current at 208-240V (kA)

10

100

65

100

100

100

100

Max Short Circuit Current at 480V (kA)

10

100

25

35

65

100

100

Max Short Circuit Current at 600V (kA)

10

100

18

25

35

65

100

1SFC100008M0201  Nov 2018

3/4

ABB AB, Control Products 

SE -721 61 Västerås, Sweden

Tel46 21 32 07 00

T46 21 12 60 01

http://www.abb.com/lowvoltage

Notice.

 

  This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances 

 

  in which case the user may be required to take adequate mitigation measures.

Hinweise.

    Dies ist ein Produkt für Umgebung A. In Haushaltsumgebung kann dieses Gerät unerwünschte Funkstörungen verursachen; in diesem Fall kann 

Notice.

 

  Ce produit a été conçu pour environnement A. L’utilisation de ce produit dans environnement B peut causer des perturbations électro-

 

  magnétiques non désirées qui, dans ce cas, peuvent obliger l’utilisateur à prendre des mesures d’atténuation appropriées.

Obs.

 

  Den här produkten har konstruerats för miljöklass A. Användning av produkten i miljöklass B kan förorsaka oönskade elektromagnetiska 

 

  störningar och i så fall krävs att användaren vidtar nödvändiga åtgärder.

Avvertenza.

 Questo prodotto è stato progettato per l’ambiente A. L’uso di questo prodotto nell’ambiente B può provocare disturbi elettromagnetici 

 

  indesiderati, nel qual caso l’utilizzatore può dover prendere adeguate misure per loro attenuazione.

Nota.

  

  Este producto ha sido diseñado para ambientes A. El uso de este producto en ambientes B puede causar perturbaciones electromagnéticas 

 

  no deseadas, en tal caso el usuario tendrá que tomar las medidas de mitigación adecuadas.

警告!  

本产品适用于环境 

A

,  在环境 

中使用本产品会产生有害电磁干扰,  在此情况下用户需采取适当防护措施.

Замечание.

 Устройство разработано для применения в средах категории А. Применение в средах категории В может привести к возникновению 

 

  нежелательных электромагнитных помех. В этом случае могут потребоваться дополнительные меры защиты от помех.

According to UL 60947-4-1 

Use wire Cu 75°C only. 

AF(S)190, AF(S)205:

 

 

Use Pressure Terminal Connectors ILSCO D-3608 (ABB ref. ATK185) or use Listed (ZMVV/7) Wire 

Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory crimp tool. Enclosure 

with min. dimension 24 by 20 by 10 inches should be used. Suitable for use on a circuit capable of delivering not more 

than the max. symmetrical amperes at the max. voltage 

shown in table 1 below

AF(S)265, AF(S)305, AF(S)370:

 

 

 Use Pressure Terminal Connectors ILSCO D-3615 (ABB ref. ATK300/2) or use Listed (ZMVV/7) 

Wire Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory crimp tool. Enclosure

with min. dimension 36 by 30 by 12 inches should be used. Suitable for use on a circuit capable of delivering not more than 

the max. symmetrical amperes at the max. voltage 

shown in table 2 below.

 

 

M 3,5

1 Nm -9Ib.in

ø 5,5

Pz 2

1 x AWG 18 ... 14

2 x AWG 18 ... 14

1 x 1 ... 4mm²

2 x 1 ... 4mm²

1 x 0,75 ... 2,5mm² 
2 x 0,75 ... 2,5mm² 

1 x 0,75 ... 2,5mm² 

2 x 0,75 ... 2,5mm² 

1 x 0,75 ... 2,5mm² 

2 x 0,75 ... 2,5mm² 

I > 3,5 mm

L < 8 mm

9 mm

L

/

1 x AWG 18 ... 14

2 x AWG 18 ... 14

Table 1

Table 2

TYPE

AF(S)190
AF(S)205

FLA

Herm. ref. comp, AC-8a

200
250

1400

250
300

400

450

520

1500

300

350

520

2100

2450

3120

LRA

AF(S)265

AF(S)305

AF(S)370

Ballast, AC-5a/

Resistance air heating

Elevator 

duty

77

99

125

144

156

A2

A1

AF(S)265, AF(S)305, AF(S)370

Circuit Breaker A

T5N600

T6S600

T6H600

T6L600

T5V600

Fuse A/Class

800L

600J

Max Short Circuit Current at 208-240V (kA)

10

100

65

100

100

100

100

Max Short Circuit Current at 480V (kA)

18

100

35

50

65

100

100

Max Short Circuit Current at 600V (kA)

18

100

20

25

35

42

100

Circuit Breaker A

T6N800

T6S800

T6H800

T6L800

Fuse A/Class
Max Short Circuit Current at 208-240V (kA)

65

100

100

100

Max Short Circuit Current at 480V (kA)

35

50

65

100

Max Short Circuit Current at 600V (kA)

20

25

35

42

T5*

T5*, T6*

Summary of Contents for AF190-30

Page 1: ...men werden Unsach gemäße Steuerspannungs oder Hochspannungsprüfungen über die Klemmen können zu Schäden an der elektronischen Steuerschaltung des Schützes führen Advertencia realizar test de alto voltaje en los terminales de bobina A1 y A2 Una tensión de control errónea o una alta tensión de test en los terminales puede dañar los circuitos electrónicos de control del contactor Avertissement que la...

Page 2: ...S 305 AF S 370 5 mm 13X 44X NC 21X 32X 22X 31X 14X 43X NO 31X 22X NO 43X 14X 44X 13X 32X 21X NC 1 2 CAL19 11 53X 84X NC 61X 72X 62X 71X 54X 83X NO 71X 62X NO 83X 54X 84X 53X 72X 61X NC 3 4 CAL19 11B 3 4 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 1 2 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 Pos 5 Pos 1 Pos 4 Pos 3 Pos 2 30 30 Pos 1 30 17X 28X 18X 27X NO NO 27X 18X 28X 17X 1 2 CEL19 10 1 2 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 NC ...

Page 3: ...я в средах категории А Применение в средах категории В может привести к возникновению нежелательных электромагнитных помех В этом случае могут потребоваться дополнительные меры защиты от помех According to UL 60947 4 1 Use wire Cu 75 C only AF S 190 AF S 205 Use Pressure Terminal Connectors ILSCO D 3608 ABB ref ATK185 or use Listed ZMVV 7 Wire Connectors and Soldering Lugs Wire connectors Cable po...

Page 4: ...el 55 of lower voltage range level 1 0 1 0 High Low Closed Open ON OFF_N Voltage Position 5 1 2 3 ON OFF_N COM Code 33 and 34 built in PLC interface Operation is controlled by separate logic control signals from for instance a PLC Use of logic control requires a steady supply voltage on A1 and A2 within the rated voltage range as described for code 11 14 The function of the logic control signal wi...