This section describes the necessary steps for inserting and removing a circuit breaker to and from the switchgear’s
“Disconnect” position. Racking the circuit breaker to and from Disconnect, Test and Connected positions is covered in the next
section. The following rules should always be observed when inserting a circuit breaker into the switchgear compartment.
NOTE:
ABB has specific accessories to be used with ABB breakers.
ALWAYS
compare the breaker ratings nameplate with the switchgear ratings nameplate. Verify breaker secondary control
voltage ratings are in agreement with the switchgear control voltage ratings.
ALWAYS
make sure lifting hooks
and lifting angles
(see photo below)
are removed prior to inserting breaker into cell.
DO NOT
attempt to insert the circuit breaker prior to a complete inspection of both breaker and switchgear compartment.
Breaker and compartment must be free of tools, obstructions or foreign objects.
DO NOT
attempt to insert or rack a closed circuit breaker.
DO NOT
force a breaker into or out of the cell.
DO NOT
remove or rotate interference blocking plate in switchgear compartment. Interference plate prevents improper
rating circuit breaker from being inserted into switchgear compartment.
INSERTION AND REMOVAL
Remove the lifting
angle before
inserting breaker in
cell
DO NOT
use Embedded
pole assemblies or primary
contacts to move or lift
breaker
Do not attempt to remove the breaker from the circuit breaker compartment without the
required ramp, dolly or lift truck. Refer to the specific switchgear Installation and
Maintenance manual for details.
WARNING
Provided
by
Northeast
Power
Systems,
Inc.
(NEPSI)
Summary of Contents for AMVAC
Page 2: ...2 1VAL050601 MB Rev C Provided by Northeast Power Systems Inc NEPSI ...
Page 46: ...46 1VAL050601 MB Rev C APPENDIX F Provided by Northeast Power Systems Inc NEPSI ...
Page 47: ...47 1VAL050601 MB Rev C APPENDIX G Provided by Northeast Power Systems Inc NEPSI ...
Page 49: ...49 1VAL050601 MB Rev C NOTES Provided by Northeast Power Systems Inc NEPSI ...