…6 Commissioning
Fitting the tamper-detection seal (FEX45X)
It is a legal requirement for MID compliant flowmeters to fit a
tamper detection seal to the remote sensor connector.
Referring to Figure 64:
1
Pass the wire of the seal through both the hole in the
locking-ring and the hole in the cable connector.
2
Close the seal.
Figure 64 Fitting the tamper-detection seal
Establish cellular 4G communication
It is necessary to establish the cellular communication of
transmitter before putting into operation. This procedure
describes how to establish cellular 4G based communication
between the transmitter and the server (refer to
1
Insert the SIM card (page 21) and set the Time Zone
according to location of installation (refer to
on page 50). Ensure that “Data Option” is
enabled in the SIM and enough balance is maintained.
Disable cellular 4G functionality through Velox.
2
Enable
Advanced Access Level Enable
in
User Access Right
Settings
and navigate to
Advanced Settings – Cellular 4G >
Operation mode
.
3
Click the edit icon and select
Disabled
and tap the phone/
tablet to the device to disable Cellular 4G communication.
4
Configure the below parameters for FTPS server through
Velox interface app under
Advance Settings – Cellular 4G
and tap the phone/tablet to the device to update the
parameters.
Item
Description
FTPS server host name
IP address: xxx.xxx.xxx.xxx
Domain name: xxx.com
FTPS server port number
e.g. 21
FTPS server username
e.g. Test
FTPS server user password
e.g. 123456
FTPS server working directory
(optional)
e.g. /test
Device folder name style
The default selection is
Meter tag
with option to select Transmitter/
Sensor ID. Ensure the
Meter tag
is
defined (refer to
Data report mode
Summary report
FTPS file type
JSON/CSV
5
Configure parameters for SSL/TLS through Velox. The
purpose of configuring SSL/TLS parameters is to realize
digital certificate based mutual authentication between the
FTPS server and the device.
a
Prepare the
CSR subject name
file (in .txt format) and
save it in the phone/tablet, the csr_info file should contain
a comma-separated list of OID (Object Identifier) types
and values as below:
Field
Description
Example
C
Country
China
CN
Common name
AquaMaster 4
L
Locality
Shanghai
O
Organization
ABB
OU
Organizational unit
Service
R
Email address
xxxx@cn.abb.com
ST
State
Shanghai
Security tag
and seal