Table 28:
Supported protocols for I/O controlling
Master protocol
IEC 60870-5-104
Modbus TCP
SNMP
Table 29:
Network interfaces
Description
Value
Ethernet ports
Ethernet/LAN
10/100 Base-T. Shielded RJ-45
1.5 kV isolation transformer
Ethernet IEEE 802-3, 802-2
Serial ports
Serial 1/Console
RS-232 DTE
Male DB-9 connector
IEC 60870-5-101 protocol support
Full serial and modem signals
300...460 800 bps
Data bits: 7 or 8
Stop bits: 1 or 2
Parity: None, Even, Odd
Flow control: None, RTS/CTS
Protection: 15 kV ESD and short circuit
Console: RS-232, 19200 bps, 8 data bits, 1 stop
bit, no parity (8N1)
Serial 2
RS-232 DTE, RS-422, RS-485 (selectable)
Male DB-9 connector
IEC 60870-5-101 protocol support
Full serial and modem signals
300...460 800 bps
Data bits: 7 or 8
Stop bits: 1 or 2
Parity: None, Even, Odd
Flow control: None, RTS/CTS
Protection: 15 kV ESD and short circuit
Section 13
1MRS758458 F
Technical data
58
ARR600
User Manual