4NWP100446R0001_OPM_ABB_AS400RelayCardPowerValue_EN140226
Page 13/15 ABB
Modifications reserved
-----------------------------------------------------------------------------
Segment 1 Function
-----------------------------------------------------------------------------
1. Utility Failure
2. Battery Low
3. General Alarm
4. Bypass Status
5. Summary Alarm
6. Battery Testing
7. Shutdown Processing
8. Over Load Warning
9. UPS On
0. Exit
-----------------------------------------------------------------------------
Please Enter Number:
Figure 19: Output function select menu
The segments’ default configuration is:
- Segment 1: Utility Failure
- Segment 2: Battery Low
- Segment 3: General Alarm
- Segment 4: Bypass Status
- Segment 5: Summary Alarm
Functions description:
1. Utility Failure: UPS input mains voltage or frequency out of range
2. Battery Low: UPS Battery voltage level is low
3. General Alarm: UPS has a failure alarm
4. Bypass Status: UPS is in Bypass mode
5. Summary Alarm: When any of the following is active, the segment will be activated: “Utility Failure”,
“General Alarm”, ”Bypass”, “Battery Low”, “Over Load Warning”
6. Battery Testing: Battery Test is in progress
7. Shutdown Processing: UPS executing shutdown after has received a shutdown command via
communication port
8. Overload Warning: UPS load is over the overload warning level defined in the specification of the UPS
9. UPS On: The UPS is powered on and is capable of providing power to the system (whether utility power is
available or not).
1.5.2.3 Input Segment Function Configure menu
The Input Segment Function menu supports the configuration and settings of the current status as indicated
in Figure 20.
--------------------------------------------------------
Input Segment Function Configure
--------------------------------------------------------
1. Segment 6 function, Current
Setting
(Battery Mode Shutdown)
2. Segment 7 function, Current Setting(UPS On)
3. Segment 8 function, Current Setting(UPS Off)
0. Exit
------------------------------------------------------
Please Enter Number:
Figure 20: Input Segment select menu
The segments’ default configuration is:
- Segment 6: Battery Mode Shutdown (Configurable)
- Segment 7: UPS On (Non-configurable)
- Segment 8: UPS Off (Non-configurable)