background image

— 

QUICK START GUIDE 

ATS Annunciator - MODBUS

ATS Annunciator monitors and controls up to 8 Automatic Transfer Switches equipped 
with the MX150/250 Controller. 

Before getting started, have the following tools and information available: 

•  PC or Laptop with USB
•  USB to RS-485 adapter - FTDI Chip USB-RS485-WE-1800-BT or similar.
•  ATS Annunciator Tool - PC graphic user interface for ATS Annunciator configuration
•  Screw Driver - Phillips #2

Summary of Contents for ATS Annunciator

Page 1: ...itches equipped with the MX150 250 Controller Before getting started have the following tools and information available PC or Laptop with USB USB to RS 485 adapter FTDI Chip USB RS485 WE 1800 BT or similar ATS Annunciator Tool PC graphic user interface for ATS Annunciator configuration Screw Driver Phillips 2 ...

Page 2: ...be attached to top and bottom or left and right sides Orient brackets for wall or flush mount 2 Mount unit to desired NEMA 1 location Step 2 Run Conduits Run conduits Between the Annunciator and all ATSs Between the Annunciator and the power source Knockouts are located on all 4 sides of the Annunciator Step 3 Ground Annunciator Ground to 6 32 stud inside box Knockouts typical Ground Lug Landing I...

Page 3: ...ically in the ATS at one or both ends of the bus 4 Terminate the PC MODBUS at its non PC end typical a The Annunciator at the non PC end of the bus Place jumper across HDR5 positions 2 3 b All other Annunciators Place jumper across HDR5 positions 1 2 Pin Signal 1 ATS MODBUS A 2 ATS MODBUS B 3 MODBUS RETURN 4 PC MODBUS A 5 PC MODBUS B MODBUS Detachable Terminal Block HDR4 16AWG max HDR5 PC MODBUS T...

Page 4: ...he Annunciator via the PC MODBUS connection through an external USB to RS 485 adapter not furnished Step 5 Connect Power Power connections are to a detachable terminal block provided attached to HDR3 see Step 4 figure Input voltage range 16 30VAC or VDC Customer supplied 24V AC or DC Class2 40VA Ground 16AWG max Plug into HDR3 6 3 1 2 4 5 2 3 4 ...

Page 5: ...ional Annunciators Remove Annunciators from the PC MODBUS network by removing their power connector or the PC MODBUS detachable block from their circuit card see Step 4 Then Disconnect and Connect the Annunciator Tool to re scan the PC MODBUS 4 To ATS MODBUS Port Settings click SUBMIT ATS 1 through ATS 8 For each desired Annunciator ATS position select the desired ATS ID from list IDs 1 247 or Non...

Page 6: ...mers associated with delaying transfer in either direction TIME DELAY SKIP Push Button Immediately skip lapse terminate T or W timer whichever is timing concurrent with pushbutton activation ATS timers will be bypassed during a test sequence if pressed before the TEST Initiate Push Button TEST IN PROGRESS LED Yellow Indicates the corresponding Transfer Switch is in a test mode Indication will occu...

Page 7: ...work 1 per Annunciator ATSs max 8 per Annunciator ATS MODBUS Network 1 per Annunciator ATS MODBUS Network 1 per Annunciator Annunciators max 32 per network Network Termination Cables 300V rated insulation Belden 9463 600V rated insulation Belden 3072F Resistors 105Ω PC AA AA AA ATS ATS ATS ATS ATS ATS ATS ATS Singly Terminated Network Daisy Chain Maximum Total Network Cable Length 500 M 1 640 ft D...

Page 8: ...ch until the Status LED turns red 5 seconds in figure in Step 4 The Status LED will be green when Reset is complete Firmware Update 1 Download the Remote Upgrade Program to the PC See Reference Documents 2 Press and release Factory Reset and Firmware Update switch until the Status LED turns red 5 seconds in figure in Step 4 The Status LED will blink red 3 Run the Remote Upgrade Program on the PC a...

Page 9: ...connected 3 Are all ATS units powered Are all ATS units equipped with network interface cards 4 Are all ATS units equipped with network interface cards Position and Source Availability LEDs Flash ON and OFF This indicates that network connections are open between annunciator and corresponding ATS 1 Is one of more ATS configured as present not None but not present on the network See Configure Annun...

Page 10: ...10 Notes ...

Page 11: ...11 Notes ...

Page 12: ... 2019 ABB All rights reserved Specifications subject to change without notice Document 850051361 19 11 ABB Zenith Controls Inc 305 Gregson Drive Cary NC 27511 24 hour support ABB Technical Services 1 800 637 1738 ...