…4 Mechanical installation
…Transmitter installation
Panel-mounting (optional)
Dimensions in mm (in)
Referring to Figure 6:
1
Cut the correct sized hole in panel
A
.
2
Insert the transmitter into the panel cut-out
B
.
3
Screw one panel clamp anchor screw
C
into the left-hand
bracket
D
until 10 to 15 mm (0.39 to 0.59 in) of the thread
protrudes from the other side of the bracket and position
one clamp
E
over the end of the thread.
NOTICE
The correct torque is critical to ensure proper compression
of the panel seal and achieve the IP66/NEMA 4X hosedown
rating.
4
Holding assembly
F
together, position bracket
D
into the
left-hand recess on the rear of the transmitter and secure
with bracket securing screw
G
. Ensure that the plastic
washer remains in the position fitted.
5
Repeat steps 3 and 4 for the right-hand panel clamp
assembly.
6
Torque each panel clamp anchor screw to 0.5 to 0.6 Nm
(4.42 to 5.31 lbf⋅in).
Figure 6 Panel-mounting the transmitter