AW T4 20 |
U N I V ER S A L 4 - W I R E , D UA L- I N P U T T R A N SM I T T ER | O I/AW T4 2 0 - EN R E V. B
41
Input/Output
Used to enable configuration of analog outputs, digital inputs and outputs and relays.
Menu
Comment
Default
Analog Outputs
The analog outputs can be configured to retransmit the process variable and temperature values and
have a configurable range from 0 to 22 mA.
HART Curr . Out
PV Range Hi
PV Range Lo
Output Value
Failure Current
See Communications Supplement
Analog Output 1 (to 4)
Analog outputs 3 and 4 are available only if an option board is fitted – see page 13.
Source
Select the sensor signal to be assigned to the output.
None
Output Type
Elec High *
Elec Low *
The output characteristic is selectable dependent on sensor type.
Eng High *
Eng Low *
Set the minimum and maximum electrical range output values within the range 0.00 to 22.00 mA.
Output Failure *
Set the minimum and maximum engineering range output values within the range of measurement
permitted by the sensor selected as the source.
Enabled
Failure Current**
Select to enable/disable the output failure function.
When enabled, the current output can be driven to a preset value if a
Failure
category diagnostic
state occurs for the selected source – see page 34.
22.0
Calibrate
AOP1(4) Trim 4 mA
AOP1(4) Trim 20 mA
Adjust 4 mA (use the
/
keys to set the mA reading to 4 mA).
Adjust 20 mA (use the
/
keys to set the mA reading to 20 mA).
Digital I/O
See page 13 for digital I/O connections.
Type
Select the
Digital I/O
type:
• Off.
• Input.
• Output.
Off
Source
Select the digital signal to be assigned to the input/output – see page <?>.
None
Polarity
Sets the polarity of the digital input/output signal – see Table 5, page 42.
Non Inverted
Relays
Relay 1 (to 4)
Source
Selects the digital signal to be assigned to the relay – see page <?>.
None
Polarity
Sets the polarity of the relay output – see Table 6, page 42.
Non Inverted
* Displayed only if
Source
is NOT set to
None
** Displayed only if
Output Failure
is set to
Enabled
Input/Output
Exit
Menu
Select