B2342
Emax VF
9/66
Doc. No
Model
Apparatus
Scale
Page No
1SDH000909R0001
4.3.2. Installation of the fixed part (Fig. 12)
Attach the fixed part by means of the screws (1), washers (2) and nuts (3) (M8 x 16), supplied by ABB SACE. if other screws are used,
make sure that the head of the screws does not extend more than 5.5 mm from the base of the fixed part.
4.4. Installation of the flange on the compartment door
(Fig. 13)
- Make the compartment door drillings specified in the “Overall dimensions” paragraph.
- Attach the flange (1) on the front of the compartment door, fixing it from the inside by means of the self-tapping screws (2).
1
2
1
2
3
Fig. 12
Note
(*) For the E2-E3 fixed parts, there
are four fixing points.
Fig. 13