Accessories
Power Panel FT50 User's manual V1.19
123
9.2.4 Device interfaces
For the technical data of the injectors, see section
.
The following graphic shows the connections of the injector:
Connections - Legend
1
Ethernet OUT port 10/100 PoE
2
Ethernet IN port 10/100
3
+24 VDC SELV power supply (18 to 32 VDC)
LEDs - Legend
4
Red
Error
(thermal shutdown or overvoltage/undervoltage detection on the in-
put)
Off
No load detected
Green
PoE in operation
Red
(blinking slowly)
Overload or short circuit detected
5
Red
(blinking quickly)
Output voltage out of range or overtemperature on PoE controller
Off
Power OFF
6
Green
Power ON
1
2
3
( )
4
( )
5
( )
6
Notice!
+24 VDC power supply
The injector may only be used in conjunction with devices that are supplied with a safe extra-low
voltage device (SELV) per EN 60950.
9.2.5 Power supply (terminal block)
Caution!
It is important to note that the pinout of the power supply differs from other B&R devices. This different
pinout is described in the following table.
In addition, there is an adhesive label with a corresponding note on the injector that must be removed
before connecting the device.
Information:
The tightening torque for securing the terminal block to the injector is 0.15 to 0.20 Nm.
Pin
Description
Figure
1
L+-
2
M
3
Functional ground
•
DC voltage terminal
•
24 AWG wire gauge
•
R/C terminal block (XCFR2), female
•
Pitch 5.08 mm
L+
M
L+
M
1
2
3
Electrical properties
Description
Value
Overvoltage category per EN 61131-2
II
Galvanic isolation
Yes
Uninterruptible power supply
No
9.2.6 Grounding
The device must always be grounded with a Cat 5 (shielded) cable. Grounding helps to limit the interference effects
on the control system through electromagnetic interference. Another way to perform grounding is to use the screws
near the connector. A label helps to identify the connection as grounding. For a more detailed overview of the
connections and pinout, see the image in the previous section.
All electronic devices in the system must be adequately grounded. Grounding must be carried out in accordance
with applicable regulations.