background image

41-337.3L

10

CA-16 relay or 14 amperes to terminals 9 and 19
of the CA-26 relay. The contacts should close
when the following operating current is applied to
the relay with connections of Figure 11.

1. CA-16

17.0 

±

7% amperes

2. CA-26

38.0 

±

7% amperes

Check each individual restraint winding by apply-
ing 50 amperes to each winding. Apply sufficient
operating current to the operating circuit until the
contacts just close. The operating current should
be:

1. CA-16

3.9 to 5.1 amperes

2. CA-26

15.8 to 18.2 amperes

C. Time Curve

Apply 20 amperes to terminals 12 and 13 of the
relays. The contacts should close in the following
times:

1. CA-16

52 

±

5% Milliseconds

2. CA-26

72 

±

5% Milliseconds

D. Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient
dc current through the trip circuit to close the
contact of the ICS. This value of current should
not be greater than the particular ICS tap setting
being used. The operation indicator target
should drop freely.

The contact gap should be approximately 0.047
inch between the bridging moving contact and
the adjustable stationary contacts. The bridging
moving contact should touch both stationary
contacts simultaneously.

E. Indicating Instantaneous Unit (IIT) – Where sup-

plied) or Fault Detector (FD)

The core screw which is adjustable from the top
of the trip unit determines the pick-up value. The
trip unit has a nominal ratio of adjustment of 1 to
4 and an accuracy within the limits of 10%.

The making of the contacts and target indication
should occur at approximately the same instant.

Position the stationary contact for a minimum of
1/32 inch wipe. The bridging moving contact
should touch both stationary contacts simulta-
neously. Apply sufficient current to operate the
IIT. Fault detector unit has no target.

F.

Sensitive Fault Detector (where supplied)

Apply current to terminals 14 and 15 of the relay.
The fault detector should operate between the
limits of 0.142 to 0.158 amperes.

7.2.

Routine Maintenance

All contacts should be periodically cleaned. A contact
burnisher Style number 182a836H01 is recom-
mended for this purpose. The use of abrasive mate-
rial for cleaning contacts is not recommended,
because of the danger of embedding small particles
in the face of the soft silver and thus impairing the
contact.

8. CALIBRATION

The use of the following procedure for calibrating the
relay if the relay has been taken apart for repairs or
the adjustments disturbed. This procedure should not
be used until it is apparent that the relay is not in
proper working order. (See “ACCEPTANCE
CHECK”).

1.

Contacts

Adjust the adjustable stop screw on the upper

disc of the relay so that a contact separation of
0.050 inch is obtained between the moving con-
tact and the stationary contact. Lock the screw
with the nut provided for the purpose.

2.

Minimum Trip

The relay should be level for this test. Minimum

trip current can best be determined with the per-
manent magnet removed.

Adjust the spring tension until the relay just

closes its contacts with the following current
applied to terminals 12 and 13 of the relay.

1. CA-16

0.15 amperes

2. CA-26

1.25 amperes

Courtesy of NationalSwitchgear.com

Summary of Contents for CA-16

Page 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Page 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Page 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Page 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Page 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Page 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Page 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Page 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Page 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Page 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Page 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Page 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Page 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Reviews: