background image

41-337.3L

11

3.

Percentage Slope Characteristic

Connect the relay per the test circuit of Figure

11. Pass 20 amperes for the CA-16 and 14
amperes for the CA-26 relay into terminals 9 and
19 of the relay. Adjust the plug (when used) in
the operating electromagnet until the contacts
just close with the following currents into the
operating circuit of the relays.

1. CA-16

29.4 to 34 amperes

2. CA-26

36 to 40 amperes

4.

Time Curve

Place the permanent magnet on the relay and

apply 20 amperes to terminals 12 and 13 of the
relay. Adjust the keeper of the permanent mag-
net until the contacts just close in the following
times.

1. CA-16

52 

±

5% Milliseconds

2. CA-26

72 

±

5% Milliseconds

These times should be the average of 5 read-

ings.

5.

Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient

dc current through the trip circuit to close the
contacts of the ICS. This value of current should
not be greater than the particular ICS tap setting
being used. The operation indicator target should
drop freely.

6.

Indicating Instantaneous Trip Unit (IIT)

The core screw must be adjusted to the value of

pick-up current desired. It is recommended that
the IIT be set to pick-up at a value of current that
is equal to the maximum rms symmetrical exter-
nal fault current to the relay.

7.

Sensitive Fault Detector

Loosen the lock nut at the top of the element and

run the core screw down until it is flush with the
top of the lock nut. Back off the Micarta disc by
loosening the two lock nuts. Apply 0.15 amperes
to terminals 14 and 15. Operate the moving ele-
ment by hand and allow the current to hold the
moving contact disc against the stationary con-
tacts. Now, screw up the core screw 

slowly

. This

causes the plunger to move up, compressing the
spring until a point of maximum deflection is
reached. Further upward motion will cause the
plunger to drop part way out of the coil, thus
diminishing the spring pressure on the contacts.
By thus adjusting the core screw up or down the
maximum spring deflection for this value of cur-
rent may be found. Then lock the core screw in
place. Next, adjust the de-energized position of
the plunger by raising the Micarta disc until the
plunger just picks up electrically at the 0.15
ampere value.

8.1.

Electrical Checkpoints

Figures 12 and 13 will aid in trouble shooting either
the CA-16 or the CA-26 relays. These curves show
the operating current to trip the relay for different
restraint current for one restraint element as well as
for six restraint elements connected in series.

9. RENEWAL PARTS

Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.

Courtesy of NationalSwitchgear.com

Summary of Contents for CA-16

Page 1: ...nt transformer accuracy class C voltage Iext maximum external fault current in secondary RMS amperes let Iext 100 if max external fault current is less than 100A Rs current transformer secondary wind...

Page 2: ...41 337 3L 2 Photo Figure 1 Types CA 16 Relay front view Photo Figure 2 Types CA 16 Relay rear view Courtesy of NationalSwitchgear com...

Page 3: ...se fluxes cause a contact opening torque 2 2 Operating Circuit The operating circuit consists of an auto transformer and an operating element The primary of the auto transformer which is the whole win...

Page 4: ...fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit t...

Page 5: ...ent transformers connected to the bus and the oper ating circuit is energized in accordance with the current flowing in the differential connection of the current transformers A current of 5 amperes i...

Page 6: ...es of the current transformers involved The time of operation of the relays is shown in Figure 6 4 2 CA 26 Transformer Relay The type CA 26 transformer differential relay includes an indicating instan...

Page 7: ...feeder ct s taking the precau tion that each feeder group has less than 14 amperes load current restraint coil continuous rating If the bus reduces to more than four circuits parallel ct s until only...

Page 8: ...9 connections where there are more than three sources the source ct s should be paralleled to reduce the effective number of source connections to three The four circuit bus connections of Figure 8 ar...

Page 9: ...of the four mounting holes on the flange for semi flush mounting or by means of the rear mounting stud or studs for projection mount ing Either a mounting stud or the mounting screws may be utilized f...

Page 10: ...acts and target indication should occur at approximately the same instant Position the stationary contact for a minimum of 1 32 inch wipe The bridging moving contact should touch both stationary conta...

Page 11: ...ve Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the top of the lock nut Back off the Micarta disc by loosening the two lock nuts Appl...

Page 12: ...41 337 3L 12 Sub 2 408C507 Figure 14 External Schematic of the Type CA 26 Relay for Wye Wye Delta Transformer Protection Sub 2 408C507 Courtesy of NationalSwitchgear com...

Page 13: ...41 337 3L 13 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 14: ...41 337 3L 14 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 15: ...41 337 3L 15 This Space Reserved for Notes Courtesy of NationalSwitchgear com...

Page 16: ...ral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Sub 16 57D7903 Figure 15 Outline and Drilling for the CA 16 and CA 26 Relays in FT...

Reviews: