ABB ABILITY™ SMART SENSOR BLUETOOTH® GATEWAY
DOCUMENT ID
REV.
DATE
LANG.
PAGE
9AKK107046A4620
L
August 2022
EN
4/29
© Copyright 2021 ABB. All rights reserved.
2
Installation
2.1
Prerequisites for installation
Internet connection:
-
Gateway does not operate in networks with a VPN (Virtual Private Network).
-
The default DNS server address is the Google DNS server for Global customers
(8.8.8.8) and the Baidu DNS server for customers located in China (114.114.114.114).
-
In case there is a firewall used, the following
ports need
to be open for
outbound
communication:
Type
Port
M/O
Communication
Partner for
Gateway
Description
UDP
5246,
5247
*
Mandatory
Access Controller
(
AC
)
Default
CAPWAP
communication between
AC and router.
Mandatory
for
FW 1.4.3
* Optional
for
FW 2.1.0
UDP
6246,
6247
Optional
Access Controller
(
AC
)
Backup
CAPWAP
communication between
AC and router.
TCP
8883
Mandatory
Access Controller
(
AC
)
MQTT
communication between AC and
router.
TCP
1883
Optional
Local
MQTT
broker
MQTT
bypass function.
TCP/HTTP
80
Optional
Access Controller
(
AC
)
Container
/
APP
download from
AC
.
TCP/HTTPS
443
Mandatory
Access Controller
(
AC
)
Smart Sensor
Platform
Container
/
APP
download from
AC
Communication with
Smart Sensor
Platform
TCP
9999
Mandatory
Access Controller
(
AC
)
Remote
SSH
to container
UDP
53
Mandatory
DNS
server
DNS
lookup for AC address
AC – Access Controller
Global:
gw.smartsensor.abb.com
China:
gw.smartsensor.abb.com.cn
Smart Sensor Platform
Global:
smartsensor.abb.com
China:
smartsensor.abb.com.cn
-
Only one AC address must be whitelisted in the network. For the gateways working
outside China, the Global AC address must be whitelisted. For gateways working
inside China, only the China AC address must be whitelisted.
-
Smart Sensor Platform and all the existing subdomains must be whitelisted in the
network for a successful communication and measurement report to the Portal.
!