CBV-2U4-3T(-N) |
Installation Overview
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
23
M
AN0
13
9
re
v
14
For UI1 Configuration, set
InputConfigA(A242)
analog setpoint to the following:
•
0 = Local Zone Temp Only (default)
•
2 = Local Zone Temp w/ Override Button
•
3 = Spare Temp or Dig In
–
Use Remote Zone Temp
For UI2 Configuration, set
InputConfigA(A242)
analog setpoint to the following:
•
0 = None or Spare Temp or Spare Dig In
•
12 = 5K Stpt Slide Adjust
For UI3 Configuration, set
InputConfigA(A242)
analog setpoint to the following:
•
0 = Discharge Air Temperature (default)
For UI4 Configuration, set
InputConfigA(A242)
analog setpoint to the following:
•
0 = None / Remote CO2 / Dehumidifier
•
32 = Local CO2
For UI4 Configuration, set
InputConfigB(A260)
analog setpoint to the following:
•
2 = Local Dehumidifier
•
1 = Local OCC Sensor
•
5 = Spare Digital Input
For the Primary State Options, set InputConfigA(A242) analog setpoint to the following:
•
0 = Switch Heat/Cool Primary Air State by Master Control
•
16 = Switch Heat/Cool Primary Air State by Supply Air Temperature
Note: To configure multiple UI settings, add numbers together for InputConfigA(A242). For example, to set UI1 for
Local Zone Temp w/Override Button and UI2 with the 5K Stpt Slide adjust, InpugConfigA(A242) will be set to
14.
Summary of Contents for CBV-2U4-3T
Page 1: ... USER GUIDE MAN0139 rev 14 CBV 2U4 3T N ...
Page 75: ......