INPUT / OUTPUT POINTS
VAV Modulating HW Reheat with 1 speed fan
AO-14
(0
…
10 Vdc)
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
DO-12
DO-13
Parallel or Series Fan
AO-14
Modulating Heat Control (0
…
10 Vdc)
AO-15
AO-16
Damper Control
(
CBV-2U4-3T
only)
VAV Modulating HW Reheat with 1 speed fan Tri-state
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button)
UI-02
Setpoint Adjustment (optional 5K slider)
UI-03
Discharge Temperature (optional)
UI-04
CO
2
, Humidity, or occupancy signal (all optional)
UI-08
Flowrate Sensor
DO-09
Damper Control (CBV-2U4-3T-N only)
DO-10
Damper Control (CBV-2U4-3T-N only)
DO-11
Heat Valve Open
DO-12
Heat Valve Close
DO-13
Parallel or Series Fan
AO-14
AO-15
AO-16
Damper Control
(
CBV-2U4-3T
only)