CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
70
M
AN0
13
9
re
v
14
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
DEFAULT VALUES
IMP STG.
MET
STG.
241
No
UnoccHeatRequest (D241)
Unoccupied heat request
On
Off
0
0
242
No
UnoccCoolRequest (D242)
Unoccupied cool request
On
Off
0
0
251
Yes
Fusion_OvrReset (D251) with
Actuator
When toggled, the FusionAir sensor will
reset all override timers. (FA Variants
only)
On
Off
253
No
PriDamperOpenCmd (D253)
Primary Damper Open Command
On
Off
0
0
254
No
PriDamperCloseCmd (D254)
Primary Damper Close Command
On
Off
0
0
257
Yes
OfflineTimerEnaBACnet (D257)
Enables offline timer test. When set to
on controller will be set to occupied
when loss of BACnet MS/TP
communication occurs
Enable
Disable
0
0
284
No
DO11CmdDisplay (D284)
If DO11 is used in strategy this point will
display on when DO 11 is commanded
on
On
Off
0
0
285
Yes
ParallelFanEnabPriAirHot (D285)
When this point is enabled, parallel fan
will be allowed to run when primary air
state is hot and there is a call for heat
Enable
Disable
0
0
296
Yes
EnabDamperPosReset (D296)
By default, when VAV is in unoccupied
mode and there is less than 10 CFM the
damper will drive shut for 100 seconds
to zero out damper position calculation
Enable
Disable
1
1
297
Yes
FusionStatLockout (D297) with
Actuator
When set to ON, temperature
adjustment will be disabled on the
FusionAir sensor. When set to OFF,
temperature adjustment is enabled on
the FusionAir sensor. (FA Variants only)
On
Off
305
No
DO12CmdDisplay (D305)
If DO12 is used in strategy this point
will display on when DO 12 is
commanded on
On
Off
0
0
306
No
DO13CmdDisplay (D305)
If DO13 is used in strategy this point
will display on when DO 13 is
commanded on
On
Off
0
0
312
Yes
DO13RevAct (D312)
When this point is enabled, DO13 will be
set for reverse acting
Enable
Disable
0
0
313
Yes
DO11RevAct (D313)
When this point is enabled, DO11 will be
set for reverse acting
Enable
Disable
0
0
314
Yes
DO12RevAct (D314)
When this point is enabled, DO12 will be
set for reverse acting
Enable
Disable
0
0
324
Yes
FusionStatLockout (D324) without
Actuator
When set to ON, temperature
adjustment will be disabled on the
FusionAir sensor. When set to OFF,
temperature adjustment is enabled on
the FusionAir sensor. (FA Variants only)
On
Off
335
Yes
Fusion_OvrReset (D335) without
Actuator
When toggled, the FusionAir sensor will
reset all override timers. (FA Variants
only)
On
Off
Summary of Contents for CBV-2U4-3T