CBV-2U4-3T(-N) |
Appendix : List of CBV-2U4-3T(-N) points
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
64
M
AN0
13
9
re
v
14
POINT SETPOINT
BLOCK
OBJECTNAME
DESCRIPTION
UNITS AND DEFAULT VALUES
IMPERIAL STG.
METRIC STG.
174
No
HeatMasterCalc (A174)
Heat Master Calculated Percent
0
%
0
%
175
Yes
HeatCapacityLimit (A175)
Point used to limit heat capacity
0
…
100%
100
%
100
%
176
No
EffFanSpeedCmd (A176)
Current variable speed fan command
0
…
100%
0
%
0
%
177
No
FanSpeedCmdAuto (A177)
Calculated variable fan speed
command
0
%
0
%
180
No
UI01_10KSensorHost (A180)
UI01 control value
0
°F
0
°C
182
No
EffHeatStpt (A182)
Active heating setpoint
0
°F
0
°C
183
No
EffCoolStpt (A183)
Active cooling setpoint
0
° F
0
°C
184
No
ZoneHeatEffCalc (A184)
Current zone heating command.
Calculation.
0
%
0
%
185
No
ZoneCoolEffCalc (A185)
Current zone heating command
calculation.
0
%
0
%
186
Yes
ManualSlaveHeatCmd (A186)
When point
is enabled this slave heating
command point can be written to
from master controller
0
…
100%.
0
%
0
%
187
Yes
ManualSlaveCoolCmd (A187)
When point
is enabled this slave cooling
command point can be written to
from master controller
0
…
100%.
0
%
0
%
190
No
ZATContrlModeEnumeration (A190)
Point can be used to determine zone
control mode
0 = Deadband mode
1 = Occupied heating mode
2 = Unoccupied heating mode
4 = Occupied cooling mode
8 = Unoccupied cooling mode
16 = Standby mode
0
no-units
0
no-units
191
No
EffZoneUnoccCoolStpt (A191)
Active unoccupied cooling setpoint
0
°F
0
°C
192
No
EffZoneUnoccHeatStpt (A192)
Active unoccupied heating setpoint
0
°F
0
°C
193
No
ZoneTempCV (A193)
Current zone control temperature
0
°F
0
°C
194
No
PriAirFlowCV (A194)
Current primary airflow
0
CFM
0
l/sec
197
No
EffPriAirFlowStpt (A197)
Current primary airflow active
setpoint
0
CFM
0
l/sec
198
Yes
LoadShedOccStptOffset (A198)
Amount of degrees that occupied
setpoints are offset when load shed
mode is enabled.
0
°F
0
°c
199
No
StrategyVer (A199)
Strategy version
200
Yes
ZoneOccCoolStpt (A200)
Occupied cooling setpoint. This
point supports priority array
75
°F
23
°c
201
Yes
ZoneOccHeatStpt (A201)
Occupied heating setpoint. This
point supports priority array
71
°F
21
°c
202
Yes
ZoneUnoccCoolStpt (A202)
Unoccupied cooling setpoint
85
°F
26
°c
203
Yes
ZoneUnoccHeatStpt (A203)
Unoccupied heating setpoint
65
°F
18
°c
204
Yes
ZoneUnoccDiff (A204)
Degrees above unoccupied heating
setpoint when heat is disabled
3
°F
3
°c
205
Yes
StandbyOffset (A205)
Amount of degrees that occupied
setpoints are offset when standby
mode is enabled.
0
°F
0
°c
206
Yes
OnBoardOccSensorOverrideTime (A206)
Amount of minutes that VAV box will
be occupied when local push button
override or motion sensor has been
activated.
60
min
60
min
207
Yes
Fusion_occOvrTime (A207)
Amount of minutes that the VAV will
be in occupied when the face of the
FusionAir sensor has been touched
120
min
120
min