Start-up
Contents of this chapter
This chapter describes the basic start-up procedure of the distributed I/O bus. The
instructions are intended for panel builders and system integrators who install drive
modules and related components (such as CIO module) into user-defined cabinet. For
the ABB cabinet-installed drives, the CIO modules are installed, wired and
commissioned at the ABB factory.
Start-up procedure
Tasks
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See
multidrive cabinets and modules safety instructions (3AXD50000048633 [English])
If you ignore the safety instructions, injury or death, or damage to the equipment can
occur.
If you are not a qualified electrical professional, do not do installation or maintenance
work.
Hardware settings
Check the mechanical and electrical installation of the drive. See the hardware manuals.
Terminate the I/O bus at its physical ends: set the termination resistor switch of the CIO module
on the rear of the I/O bus to ON position and terminate the other end of the I/O bus on the BCU
or UCU control unit. Set intermediate termination resistors to OFF position.
Switch on the auxiliary power to the CIO modules.
Note: Fan power supply must remain de-energized.