![background image](http://html1.mh-extra.com/html/abb/com600-series/com600-series_product-manual_3381037014.webp)
ABB
14
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 11. Environmental tests
Description
Standard
Dry heat test
According to IEC 60068-2-2
Test values:
• 96 h at +55ºC
• 4 h at +70ºC
Cold test
According to IEC 60068-2-1
Test values:
• 96 h at -10ºC
• 4 h at -25ºC
Damp heat test, cyclic
According to IEC 60068-2-30
Test values:
• 6 cycles (12+12h) at
+25…55°C, humidity >93%
Storage test
According to IEC 60068-2-48
Test values:
• 72 h at +70ºC
• 72 h at -40ºC
Table 12. Mechanical tests
Description
Standard
Vibration tests
• Vibration response test
• Vibration endurance test
According to IEC 60068-2-6 and
IEC 60255-21-1
f = 10...150 Hz, ± 0.035 mm,
10…58 Hz,
5 m/s2 58…150 Hz
f = 10...150 Hz, ± 0.075 mm,
10…58 Hz, 10 m/s2 58…150
Hz
Shock and bump tests
•
Shock response test
•
Shock withstand test
•
Bump test
According to IEC 60068-2-27 ,
IEC 60068-2-29 and IEC 60255-
21-2
peak acceleration = 5 x gn,
pulse duration = 11 ms, num-
bers of pulses in each diretion
= 3
peak acceleration = 15 x
gn, pulse duration = 11 ms,
number of pulses in each direc-
tion = 3
peak acceleration = 10 x
gn, pulse duration = 16 ms,
number of pulses in each direc-
tion = 1000