SETUP
PROCESS LOOP SETUP
3 - 4
PROCESS LOOP SETUP
Loop Tag Name
1. From the setup menu, press or to highlight
LOOP 1
. Press
. The loop label menu will appear.
The loop tag name is a user-defined character string depicting the tag
name for the selected loop. The maximum number of characters
allowed is 14. Tag names less than 11 characters will appear on the
display in a larger font. Valid characters are A to Z, 0 to 9, - (hyphen),
*, (, ), /, ° and '.
Tagname
2. If
Tagname
is not highlighted, press or until it is. Press
.
The cursor will appear on the left side of the screen and the soft key
menu will be displayed. Choose the characters for the description.
Press or until the character appears and then press the soft key
below
←
or
→
to move the cursor to the next position. Once the tag
name characters have been entered, press
.
PV and Set Point
Engineering Units
The process variable and set point engineering units are user-defined
character strings depicting the name of the units of the values. The
maximum number of characters allowed is five. Valid characters are A
to Z, 0 to 9, - (hyphen), *, (, ), /, ° and '.
PV EU
SP EU
3. Press
or
until
PV EU
is highlighted. Press
. Select the
process variable engineering units. Press or until the character
appears and then press the soft key below
←
or
→
to move the cur-
sor to the next position. Once the engineering unit characters have
been entered, press
. Repeat this step to set the engineering
units for the set point (
SP EU
).
Decimal Places
This value controls the maximum number of digits after the decimal
point is displayed on process display screens. Setting this number to
four allows the value to be displayed with the most number of decimal
places. For example, if the process variable has a range of zero to
100, normal display would include a maximum of one decimal place.
Changing this number to zero limits the display to zero decimal
places. Selecting one or less decimal places causes the displayed
value to be shown in a larger font.
L1: BYP
L2: BYP
SETUP
LOOP 1
LOOP 2
MODBUS ADDR
D.O. LOCKOUT
SECURITY
DIAGNOSTIC
OPTIONS
BRIGHTNESS
s
t
SEL
1
s
t
SEL
s
t
SEL
s
t
SEL
s
t
SEL