2. For controllers with the optional frequency input, press
when
FREQUENCY
is highlighted and the DI3 setup screen appears.
Press
and
a
NO/YES
box will appear on the screen. Press or
to select. When the correct input is highlighted, press
to con-
firm the entry. Press the soft key below
PREV SCRN
to return to the
setup/option board menu.
SETUP AI3
This option allows defining analog input three as a temperature input.
An option board must be installed with the main board jumpers set in
order for a temperature input to be used (Fig.
D-1
). Function code
182 N output (mV) must be referenced to S3 of function code 230 at
block 100 (Fig.
A-2
).
3. For controllers with the optional temperature input that replaces
the standard AI3 input, press
when
SETUP AI3
is highlighted.
An
AI3 TEMP
setup screen appears. Press
and a
NO/YES
box
will appear on the screen across from
INP:.
Press or to select
YES
, then press
. Press or to select
TYPE
. Press
and
a box will appear with an input selection list. Press or to scroll
through the input list. When the correct input is highlighted, press
.
Set the engineering units (
EU
) in degrees Celsius or Fahrenheit. To
set the resistance (
L/W RES [OHMS]
), press
. A new soft key
menu will appear and a cursor will be under the first zero to the right
of the decimal. Use the soft keys below
←
and
→
to position the cur-
sor and press or to establish the correct value. When complete,
press
. Press the soft key under
PREV SCRN
. A warning will
appear.
NOTES:
1.
Whenever the
ESC
soft key menu option is shown, pressing the
soft key directly below it deletes the entered information for that
function and the correct information can be entered.
2.
For controllers with optional temperature inputs, in addition to
completing Step
, also complete a calibration procedure for tem-
perature inputs. These screens are listed as
CAL AI3
and
CAL AI4
.
SEL
SEL
s
t
SEL
L1: MAN
L2: MAN
SETUP
AI3 TEMP
INP: [YES/NO]
TYPE: [MVOLT]
EU: [DEG C]
L/W RES (OHMS):
0.000
Input Selection List
UNDEFINED
MVOLT
S T/C
R T/C
E T/C
J T/C
K T/C
T T/C
CH E T/C
CH S T/C
2/100 LAB
2/100 IND
2/100 EUR
2/PURE NI
3/100 LAB
3/100 IND
3/100 EUR
3/PURE NI
PREV
SCRN
PROC
DSPL
SEL
SEL
s
t
SEL
s
t
SEL
s
t
SEL
3
SEL
s
t
SEL