CONTROL CONFIGURATION LEVEL
•
Ramp/Soak
2.2
Ramp/Soak Profile Control
In this Section, parameters in the lower display denoted
■
are Company Standard Settings. The instrument is dispatched
programmed with these settings.
Active
Inactive
Run
PrOFLE
CONtrL
SELECt
NONE
CtrL 1
PrOFLE
r–h.Src
NONE
SEG 99
run.Src
HLd.Src
SKIP–F
ON
SEG 99
NONE
NONE
CtrL 2
OFF
t–UNIt
MINS
HOUrS
OFF
SEG 99
NONE
SEG 99
SKIP–b
NONE
SEG 99
NONE
Page Header – Profile Control.
To advance to the
Profile Program
page press the
switch.
Select Controller
Select the Controller to be programmed:
CtrL 1
–
Controller 1
CtrL 2
–
Controller 2 (if fitted)
NONE
–
No controller selected
Ramp/Soak Profile Enable
If
ON
is selected, Profile Control is enabled and the
Profile States Page
is displayed in the
OPERATOR LEVEL
. If
OFF
is selected Profile Control is disabled and the
Profile States Page
is
omitted from the
OPERATOR LEVEL
.
Program Time Units
Select the time units required:
MINS
–
Minutes
HOUrS
–
Hours
The time base selected applies to all segments.
Program Run/Hold Source
Select the source required to activate program run/hold. The run/hold source is level triggered i.e.
the active logic state must be maintained to select the alternative function.
If a program is activated or placed into operator hold mode
using
Program Run/Hold Source
, the
Program Run Source
and
Program Hold Source
have no effect.
For description of sources for this and subsequent source frames, refer to table 2.1 on page 10.
Program Run Source
Select the source required to run or restart a program. The run source is leading edge
triggered i.e. the active logic state can be removed after the
function is selected.
Program Hold Source
Select the source required to place the program running into operator hold mode. The hold
source is leading edge triggered.
The program is restarted using the
Program Run Source.
Segment Skip Forward Source
Select the source required to skip to the next segment. If the segment running is the last segment
of the program, the set point advances to the last set point value of the segment and stops the
program. The skip source is leading edge triggered.
Segment Skip Backward Source
Select the source required to skip back to the beginning of the ramp/soak segment running. The
skip source is leading edge triggered.
Continued on next page.
Active
Inactive
Run
Hold