60
0
A.PA5
b.07
00.00
t.CLK
b..15
0
C.PA5
b.11
0
S.PAS
b.10
1
dAY
b..12
23
HOUr
b..13
59
MIN
b..14
•1
LEVb
OPEr
59
b.INC
b..16
b.07...b.16
…4
CONFIGURATION MODE
…4.7
Level B – Operator Configuration
Auto-tune Password
Enables access to the auto-tune facility in the operator level.
[0 to 9999 (default 0)]
Set Up Password
Enables access to the set up levels (levels 2, 3, 4 and 5) and the autotune
facility.
[0 to 9999 (default 0)]
Configuration Password
Enables access to the configuration levels, set up levels and the autotune
facility.
[0 to 9999 (default 0)]
Day Setting
Use to set the weekday of the on-board clock.
[1 to 7. 1 = Sunday, 7= Saturday]
Hour Setting
Use to set the hour of the on-board clock.
[0 to 23]
Minute Setting
Use to set the minute of the on-board clock.
[0 to 59]
Current Time
Actual on-board clock time.
[Hours : Mins]
Bargraph Increment
Deviation represented by each bargraph element.
[1 to 10% of engineering range]
Return to top of page.
•1
Not displayed on Indicator or Auto/manual station templates.