Section-2
04-3008_S2_ABB_OPMCPDPA-S2_GB_121202
Page 12/16 ABB
Printed in Switzerland – Modifications reserved
2.3.1.2
Internal Battery Modules TRIPLE DPA-150
In
Conceptpower DPA
TM
S2
CLASSIC DPA-50 FRAME
there is space for up to
240 x 9Ah internal batteries.
In the drawing below different Battery and System configurations are shown. The batteries may be used as
separate batches for each UPS-Module or they can be used as common batteries for all tree UPS-Modules.
NOTE
: For UPS-Systems DPA 30kVA and DPA 50kVA it is allowed to use 40-50 (only even numbers) of 12V-
battery blocks.
NOTE
: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).
CONCEPTPOWER TRIPLE DPA-150
3x(2x40)x7Ah
Other combination possible : refer to Section 10
DPA TRIPLE 150 frame