16
12.3.2
Mounting
The toothed gear pair of the position sensor is held in place by a tension spring (3), to ensure sufficient
free motion when the direction of rotation is reversed.
-
fasten sensor cable plug on sensor pcb
-
set the stop pin to the center position, as shown in Figure 14
-
align the sensor and its gears with the actuator; set the first toothed gear in 03:00 o’clock position
(see Figure 15) onto the drive shaft gear (4)
-
slightly move the sensor back and forth to pre-tension the toothed gears with the difference “z“ until
the second toothed gear snaps in
-
fasten the screws (1) tightly
)
After mounting is completed readjust the actuator range as described in setup section of this manual.
Figure 14: Position sensor SP 1
Figure 15: Mounting position of SP 1
Z
1
2
1
3
(r00329x1)
(r0151rxa)
position sensor
sensor cable