CO NTRO LM A STE R CM 10
| U N I V ER S A L P R O C E S S CO N T R O L L ER , 1/8 D I N | C I/C M 10 - EN R E V. C
23
Icon
Number/
Message
Possible cause
Suggested action
086.036
Oscillation 1
Abnormal oscillations in the control loop.
Check process.
Perform new manual or Autotune.
094.034
Valve 1
Sticking
Motorized valve travel time is significantly
slower than configured time.
Check valve to identify reason for sticking.
Check correct travel time is entered in configuration.
168.026
(166.027)
(164.028)
Tuner 1
Phase 1..3
Autotune is in progress.
Autotune can be aborted if required by selecting Manual control
mode.
162.029
(154.033)
Tuner 1 Pass
Autotune has completed successfully and
calculated new control parameters.
Acknowledge diagnostic.
178.025
In
Configuration
The device is currently in the configuration
mode.
This is for use with remote access via digital communications.