14
Electromagnetic Flowmeter
COPA-XE / MAG-XE
Submenu/Parameter
Entry Type
Comments
from table
This menu is not displayed for Profibus DP or ASCII-Communica-
tion. For the HART-Protocol the current output is fixed at 4-20 mA!
If an Instrument Address greater than 0 is set in the Submenu
Data Link for HART Protocol, the instrument operates in the
Multidrop Mode. The current output is fixed at 4-20 mA.
Selections: 0-20 mA / 4-20 mA, 0-10 mA / 2-10 mA, 0-5 mA /
0-10 mA, 10-20 mA / 4-12 mA, 12-20 mA
Current output settings during an alarm condition, 0%; 3.8 mA or
130%. For Error 3 (Flowrate > 130%), always 130%
from table/numeric
Exit the submenu
The Submenu Data Link is only visible when that option has been
ordered and recognized by the converter.See ASCII-, HART- or
Profibus-Communication Instruction Bulletins for the appropriate
option for more detailed information.
Profibus DP, Profibus PA, ASCII, ASCII2w.
Communication Profibus PA
(available if meter with this option has been ordered)
With Profibus PA communication the menu-structure will be as fol-
lows:
This is for information purposes only.
There is no further parameter-setting pos-
sible. Instrument address is 126 (Default
Value). The address can be changed by
Profibus communication on the bus.
HART protocol communication
(available if meter with this option has been ordered)
With HART-protocol communication the menu-structure will be as
follows:
This is for information purposes only.
There is no further parameter-setting
possible.
For HART-protocol, Instrument address:
0-15. (Multidrop-Mode for addresses
greater than 0)
Communication Profibus DP or ASCII-Communication
(available if meter with this option has been ordered)
With Profibus DP or ASCII communication the menu-structure will
be as follows:
Profibus DP, ASCII or ASCII2w are
selectable.
The instrument address on the Profibus
DP can be set accessing this menue or by
Profibus DP communication on the bus
itself. The instrument address has to be
set using 3 digits (e.g. 065). Range of
addresses: 0-126. Default Value: 126
Submenu
Current Output
ENTER
Current Output
0 - 20 mA
Iout at Alarm
130 %
Submenu
Data Link
C/CE
ENTER
Communication
ASCII
Instr. Address
004
Communication
Profibus PA
Communication
HART
Instr.address
000
Communication
Profibus DP
Slave-Adr.
008