EX Safety Instructions 

SI/FCM2000/FM/CSA-EN 

 

Mass Flowmeter 

CoriolisMaster FCM2000 

  

 

 
 

cFMus Div. 1, Div. 2 

 
 

 

 

 

 

 

Safety information for electrical 
equipment for potentially explosive areas 
in accordance with Factory Mutual 
Standards and Canadian Standards 
Association 

Mass Flowmeter 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

 
 

 

 

 

 

 

 

 

 

 

 

 

  

 

Summary of Contents for CoriolisMaster FCM2000

Page 1: ...M CSA EN Mass Flowmeter CoriolisMaster FCM2000 cFMus Div 1 Div 2 Safety information for electrical equipment for potentially explosive areas in accordance with Factory Mutual Standards and Canadian St...

Page 2: ...ucts GmbH Measurement Analytics Dransfelder Stra e 2 D 37079 G ttingen Germany Tel 49 551 905 0 Fax 49 551 905 777 Customer service center Phone 49 180 5 222 580 Fax 49 621 381 931 29031 automation se...

Page 3: ...3 Mounting 8 3 1 Installing the field mount housing 8 3 2 Cable entries 8 3 3 Electrical connection 9 3 4 Process sealing 10 4 Ex relevant specifications 11 4 1 Data relating to MS2x operation 11 4 1...

Page 4: ...hnical limit values Particular attention must be paid to the limit values listed in the sections relating to ex relevant specifications The data for the signal inputs and outputs of the transmitter Th...

Page 5: ...formation may result in death or severe injury WARNING Bodily injury This symbol in conjunction with the signal word Warning indicates a potential electrical hazard Failure to observe this safety info...

Page 6: ...10 A0281 NI CL I II III DIV 2 GP ABCDEFG Control Install Dwg No MDM 10 A0291 Ex d e ia IIC T6 Ex d e ia ib IIC T6 DIP A21 TA T115 C Tfluid CL II DIV 1 GP EFG Control Install Dwg No MDM 10 A0281 XP CL...

Page 7: ...ype ME22 23 T X MS21 T X ME22 23 O V P W MS21 O V P W ME27 28 C Y D Q MS26 C Y D Q 1 Remote mount design small nominal diameters Transmitter Standard non Ex Class I Div 1 Flowmeter sensor Class I Div...

Page 8: ...must be observed If direct sunlight cannot be avoided an appropriate form of sun protection must be installed For FNICO or FISCO installations the number of devices must be limited as per the applica...

Page 9: ...58 F at the cable entry is assumed for the Ex calculations Therefore the cables used for the supply power and the signal inputs and outputs must have a minimum specification of 70 C 158 F According to...

Page 10: ...cess fluids and are installed within a process pipe Among others the instruments are connected to an electrical system via a conduit system which is able to allow the migration of process fluids direc...

Page 11: ...t design the signal cable between the flowmeter sensor and the transmitter must measure at least 5 m 16 4 ft Ambient and process conditions Tamb 40 50 C 40 122 F TMedium 50 180 C 58 356 F Protection c...

Page 12: ...sive switchable Contact input and output passive 4 2 1 Electrical data relating to Div 1 Version I Active Passive current outputs Types ME26 27 28 Active HART Type of protection IS Inputs and outputs...

Page 13: ...ircuits It is not permitted to combine intrinsically safe and non intrinsically safe circuits On intrinsically safe circuits equipotential bonding must be in place along the entire length of the cable...

Page 14: ...minal 33 34 30 30 Digital output Terminal 41 42 30 65 Digital input Terminal 81 82 30 10 Pulse output Terminal 51 52 30 65 All inputs and outputs are electrically isolated from each other and from the...

Page 15: ...transmitter must be grounded in accordance with the applicable international standards The connecting cables and connections must be adequate for the anticipated current intensities and must meet the...

Page 16: ...mage or explosion can be detected NI 500 VAC 1 min or 500 x 1 414 710 VDC 1 min test between terminals 31 32 33 34 41 42 51 52 81 82 and or 97 98 and terminals 31 32 33 34 41 42 51 52 81 82 97 98 and...

Page 17: ...connection lines and wait at least 20 minutes WARNING Electrical voltage risk When the housing is open EMC protection is impaired and protection against contact is suspended Before opening the housin...

Page 18: ...Appendix 18 CoriolisMaster FCM2000 SI FCM2000 FM CSA EN 7 Appendix 7 1 Installation drawing MDM10 A0281 Page 1 of 2...

Page 19: ...Appendix SI FCM2000 FM CSA EN CoriolisMaster FCM2000 19 Page 2 of 2...

Page 20: ...Appendix 20 CoriolisMaster FCM2000 SI FCM2000 FM CSA EN 7 2 Installation drawing MDM10 A0291 Page 1 of 2...

Page 21: ...Appendix SI FCM2000 FM CSA EN CoriolisMaster FCM2000 21 Page 2 of 2...

Page 22: ...tive PED 2014 68 EU RoHS Directive 2011 65 EC Pressure equipment does not feature a CE mark indicating PED compliance on the factory tag if the following conditions prevail The maximum permissible pre...

Page 23: ...Notes SI FCM2000 FM CSA EN CoriolisMaster FCM2000 23 Notes...

Page 24: ...FCM2000 FM CSA EN Rev C 3KXF411003R4801 ABB Limited Measurement Analytics Howard Road St Neots Cambridgeshire PE19 8EU UK Tel 44 0 870 600 6122 Fax 44 0 1480 213 339 Mail enquiries mp uk gb abb com A...