Installation
22 - EN
CoriolisMaster FCM2000
CI/FCM2000-EN
Design ME26 for flowmeter sensor MC2
Zone 1
Designation
ATEX
Version II/III
II 2 G Ex d e [ia] [ib] IIC T6
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
II 2 G Ex d e [ib] IIC T6
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
Version I/II/III
II 2 D Ex tD A21 IP6X T115 °C
Outputs "e"
Version II/III
II 2 D Ex tD [iaD] A21 IP6X T115 °C
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
II 2 D Ex tD [ibD] A21 IP6X T115 °C
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
Version III
FISCO field device FISCO
fieldbus
IECEx
Version II/III
Ex d e [ia] [ib] IIC T6
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
Ex d e [ib] IIC T6
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
Version I/II/III
Ex tD A21 IP6X T115 °C
Outputs "e"
Version II/III
Ex tD [iaD] A21 IP6X T115 °C
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
Ex tD [ibD] A21 IP6X T115 °C
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
Version III
FISCO field device FISCO
fieldbus
Design ME27/ME28 for flowmeter sensor MS2
Zone 1
Designation
ATEX
Version II/III
II 2 G Ex d e [ia] [ib] IIC T6
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
II 2 G Ex d e [ib] IIC T6
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
Version II/III
II 2 D Ex tD [iaD] A21 IP6X T115 °C
2 passive analog outputs, outputs "ia"/"e", depending on user
wiring, or FISCO fieldbus
Version I
II 2 D Ex tD [ibD] A21 IP6X T115 °C
Active/passive analog outputs, outputs "ib"/"e", depending on
user wiring
FISCO field device
FISCO fieldbus
Pos: 19.12 /Standard-Layout/Hinweise/Wichtig/Wichtig - Hinweis auf SM EX-Sicherheitshinweise für FM (OI/CI) @ 29\mod_1243411932812_3101.doc @ 273191 @ @ 1
Important
When using the device in explosion hazardous areas, the additional temperature
specifications in the section titled "Ex relevant specifications" on the data sheet or in the the
separate Ex safety instructions (SM/FCM2000/FM/CSA) must be observed.