background image

41-116.1A

4

reclosing will be initiated immediately after a trip by
the CO contact, the time of the opening of the con-
tacts should be a minimum. This condition is
obtained by loosening the stationary contact mount-
ing screw, removing the contact plate and then
replacing the plate with the bent end resting against
the contact spring.

For double trip relays, the upper stationary contact is
adjusted such that the contact spring rests solidly
against the back stop. The lower stationary contact is
then adjusted such that both stationary contact make
contact simultaneously with their respective moving
contact.

4.2. INDICATING CONTACTOR SWITCH (ICS)

There are no settings to make on the indicating con-
tactor switch (ICS).

4.3. INDICATING INSTANTANEOUS TRIP (IIT)

The proper tap must be selected and the core screw
must be adjusted to the value of pick-up current
desired.

The nameplate data will furnish the actual current
range that may be obtained from the ITT unit. It is
recommended that the IIT be set on the higher tap
where there is a choice of tap settings. For example,
for a 20 ampere setting use the 20 to 50 tap rather
than the 6 to 20 tap.

4.4. VOLTAGE UNIT (V)

The voltage unit

spring calibration is set to close its

contact when the applied voltage is reduced to 80
volts. The voltage unit can be set to close its contacts
from 80 volts to 100 volts

by adjusting the resistor

located at the top left of the voltage unit. The spiral
spring is not disturbed when making any setting other
than the calibrated setting of 80 volts.

5. INSTALLATION

The relays should be mounted on switchboard pan-
els or their equivalent in a location free from dirt,
moisture, excessive vibration and heat. Mount the
relay vertically by means of the four mounting holes
on the flange for the semi-flush type FT case. The
mounting screws may be utilized for grounding the
relay. External toothed washers are provided for use
in the locations shown on the outline and drilling plan
to facilitate making a good electrical connection
between the relay case, its mounting screws and the

relay panel. Ground wires should be affixed to the
mounting screws as required for poorly grounded or
insulated panels. Other electrical connections may
be made directly to the terminals by means of screws
for steel panel mounting.

For detail information on the FT case refer to IL
41-076 for semi-flush mounting.

6. ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct operation of
this relay have been made at the factory. Upon
receipt of the relay, no customer adjustments, other
than those covered under “SETTINGS”, should be
required.

The Indicating Instantaneous Trip unit (IIT) used in
some relays requires a much higher current for trip-
ping than is required by the other units. For this rea-
son, the junction of the CO unit coil and the IIT unit
coil is brought out to switch jaw no. 3 (whenever it is
available) to permit the testing of these units sepa-
rately.

When applying current in excess of 50 amperes
to test the IIT, the current should not be left on
while adjusting it to the trip level. Instead, apply
the current in short bursts, not more than 2 sec-
onds long, to check for tripping. Make adjust-
ments in the current control while the current is
off.

High currents left on for excessive time periods
can result in the softening and possible melting
of insulation the interconnecting wires.

6.1. OPERATIONAL CHECK

The following check is recommended to insure that
the relay is in proper working order. (See Figure 9.)

6.1.1. Overcurrent Unit (CO)

The directional unit contacts must be in the closed
position and the “T” unit picked up when checking the
operation of the overcurrent unit.

A. Contact

1) By turning the time dial, move the moving

!

CAUTION

Summary of Contents for COV-11

Page 1: ...ncy shutdown of the reactor containment isolation cooling of the reac tor and heat removal from the containment and reac tor or otherwise are essential in preventing significant release of radioactive material to the environment The type COV relay is applicable where it is desired that an overcurrent unit be set to operate on less than full load current when the voltage falls below a prede termine...

Page 2: ...locking nut The bearing can be replaced if necessary without having to remove the magnetic core from the frame The electromagnet has two pairs of voltage coils Each pair of diametrically opposed coils is connected in series In addition one pair is in series with an adjustable resistor These sets are paralleled as shown in Figure 2 The adjustable resistor serves not only to shift the phase angle of...

Page 3: ...NIT CO Since the tap block screws carry operating cur rent be sure that the screws are turned tight In order to avoid opening current transformer cir cuits when changing taps under load start with RED handles FIRST and open all switchblades Chassis operating shorting switches on the case will short the secondary of the current trans former Taps may then be changed with the relay either inside or o...

Page 4: ...ange for the semi flush type FT case The mounting screws may be utilized for grounding the relay External toothed washers are provided for use in the locations shown on the outline and drilling plan to facilitate making a good electrical connection between the relay case its mounting screws and the relay panel Ground wires should be affixed to the mounting screws as required for poorly grounded or...

Page 5: ...op the index mark is offset to the right of the O mark by approximately 020 The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time current curves For double trip relays the follow on the stationary contacts should be approximately 1 32 B Minimum Trip Current Set the time dial to posi tion 6 Alternately apply tap value ...

Page 6: ...e should not be used until it is apparent that the relay is not in proper working order see Operational Check NOTE A spring shield covers the reset spring of the CO unit To remove the spring shield requires that the damping magnet be removed first The screw connection holding the lead to the moving contact should be removed next The second screw holding the moving contact assem bly should then be ...

Page 7: ... e g COV 8 20 times tap value and measure the operating time Adjust the proper plug until the operating time corresponds to the value in Table 1 Withdraw ing the left hand plug front view increases the operating time and withdrawing the right hand plug front view decreases the time In adjusting the plugs one plug should be screwed in com pletely and the other plug run in or out until the proper op...

Page 8: ...ing position is fixed and cannot be adjusted B The contact gap adjustment for the directional unit is made as follows With the moving contact in the normally closed position i e against the left stop on bridge screw in the stationary contact until both con tacts just close as indicated by a neon lamp in the contact circuit Then screw the stationary contact in toward the moving contact an addi tion...

Page 9: ... 4 37 20 6 20 7 21 0 21 4 23 2 24 9 26 2 103 106 114 122 147 168 180 270 288 325 360 462 548 630 2 6 2 2 5 3 3 5 4 5 6 8 0 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 67 66 64 63 62 59 57 3 88 3 90 3 93 4 09 4 12 4 20 4 38 21 0 21 6 22 1 23 1 23 5 24 8 26 5 110 118 126 136 144 162 183 308 342 381 417 448 540 624 4 12 4 5 6 7 8 10 12 16 0 18 8 19 3 20 8 22 5 25 0 28 0 460 460 460 460 46...

Page 10: ...4 5 6 8 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 66 63 63 63 61 59 58 4 06 4 07 4 14 4 09 4 34 4 40 4 62 21 3 21 8 22 5 23 1 23 8 25 2 27 111 120 129 136 149 163 183 306 342 366 417 448 530 624 4 12 4 5 6 7 8 10 12 16 18 8 19 3 20 8 22 5 25 28 460 460 460 460 460 460 460 64 61 60 58 55 51 46 4 24 4 30 4 62 4 69 4 80 5 20 5 40 22 8 24 2 25 9 27 3 29 8 33 37 5 129 149 168 187 211 260 ...

Page 11: ...nuous Rating Amperes One Second Rating Amperes Power Factor Angle Ø VOLT AMPERES At Tap Value Current At 3 Times Tap Value Current At 10 Times Tap Value Current At 20 Times Tap Value Current 0 5 2 5 0 5 0 6 0 8 1 0 1 5 2 0 2 5 1 7 1 9 2 2 2 5 3 0 3 5 3 8 88 88 88 88 88 88 88 36 34 30 27 22 17 16 0 72 0 75 0 81 0 89 1 13 1 30 1 48 6 54 6 80 7 46 8 30 10 04 11 95 13 95 71 8 75 0 84 0 93 1 115 5 136 ...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...41 116 1A 21 Figure 11 Outline and Drilling Plan for the Type COV Relay in Type FT21 Case 3519A66 Sub 4 ...

Reviews: