background image

41-116.1A

8

a) Contact Wipe – Adjust the stationary contacts

so that both stationary contacts make with the
moving contacts simultaneously and wipe 1/4”
to 3/64” when the armature is against the core.
This can be accomplished by inserting a .0125
thick gage between the armature and case and
adjusting the stationary contacts until they just
touch the moulding.

b) Target – Manually raise the moving contacts and

check to see that the target drops at the same
time as the contacts make or up to 1/16” ahead.
The cover may be removed and the tab holding
the target reformed slightly if necessary. How-
ever, care should be exercised so that the target
will not drop with a slight jar.

c)

Pickup – Place tap screw in the 6 to 20 tap and
turn the core screw all the way in. contacts
should pickup at a value of current less than 6
amperes but not lower than 5.1 amperes. If
pickup is above this range, it may be reduced by
using a tweezer or similar tool and squeezing
each leaf spring approximately equal by applying
the tweezer between the leaf spring and the front
surface of the cover at the bottom of the lower
window. If the pickup is below range it may be
increased by removing the front cover and bend-
ing the leaf spring outward equally. an approxi-
mate adjustment would be when the end of the
leaf spring is in line with the edge of the molded
cover. The described pickup is obtained by set-
ting the tap screw in the proper range and adjust-
ing the core screw.

7.4. Voltage Unit (V)

A. The upper pin bearing should be screwed down

until there is approximately. 0.25” clearance
between it and the top of shaft bearing. The
upper pin bearing should then be securely locked
into position with the lock nut. The lower bearing
position is fixed and cannot be adjusted.

B. The contact gap adjustment for the directional

unit is made as follows:

With the moving contact in the normally-closed
position i.e., against the left stop on bridge,

screw in the stationary contact until both con-
tacts just close as indicated by a neon lamp in
the contact circuit. Then, screw the stationary
contact in toward the moving contact an addi-
tional one-half turn. The clamp holding the sta-
tionary contact housing need not be loosened for
the adjustment since the clamp utilizes a spring-
type action in holding the stationary contact in
position.

C. The sensitivity adjustment is made in two steps:

1) The adjustable resistor, located at the top left

of the voltage unit, is adjusted such that the
maximum resistance is in the circuit (approxi-
mately 2500 ohm).

2) The tension of the spiral spring, attached to

the moving element assembly, is then varied.
The spring is adjusted by placing a screw-
driver or similar tool into one of the notches
located on the periphery of the spring
adjuster and rotating it. The spring adjuster is
located on the underside of the bridge and is
held in place by a spring type clamp that does
not have to be loosened prior to making the
necessary adjustments.

The spring is to be adjusted such that the contacts
will close (indicated by pickup of telephone relay “T”)
when the applied voltage is reduced to 80 volts. The
contacts should open with 80 plus volts applied.

Any setting other than the 80 volts then can be made
by adjusting the resistor for the desired contact clos-
ing voltage.

8. RENEWAL PARTS

Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to the customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.

Class 1E certification of a repaired relay is the
responsibility of the agent who makes the repair.

Summary of Contents for COV-11

Page 1: ...ncy shutdown of the reactor containment isolation cooling of the reac tor and heat removal from the containment and reac tor or otherwise are essential in preventing significant release of radioactive material to the environment The type COV relay is applicable where it is desired that an overcurrent unit be set to operate on less than full load current when the voltage falls below a prede termine...

Page 2: ...locking nut The bearing can be replaced if necessary without having to remove the magnetic core from the frame The electromagnet has two pairs of voltage coils Each pair of diametrically opposed coils is connected in series In addition one pair is in series with an adjustable resistor These sets are paralleled as shown in Figure 2 The adjustable resistor serves not only to shift the phase angle of...

Page 3: ...NIT CO Since the tap block screws carry operating cur rent be sure that the screws are turned tight In order to avoid opening current transformer cir cuits when changing taps under load start with RED handles FIRST and open all switchblades Chassis operating shorting switches on the case will short the secondary of the current trans former Taps may then be changed with the relay either inside or o...

Page 4: ...ange for the semi flush type FT case The mounting screws may be utilized for grounding the relay External toothed washers are provided for use in the locations shown on the outline and drilling plan to facilitate making a good electrical connection between the relay case its mounting screws and the relay panel Ground wires should be affixed to the mounting screws as required for poorly grounded or...

Page 5: ...op the index mark is offset to the right of the O mark by approximately 020 The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time current curves For double trip relays the follow on the stationary contacts should be approximately 1 32 B Minimum Trip Current Set the time dial to posi tion 6 Alternately apply tap value ...

Page 6: ...e should not be used until it is apparent that the relay is not in proper working order see Operational Check NOTE A spring shield covers the reset spring of the CO unit To remove the spring shield requires that the damping magnet be removed first The screw connection holding the lead to the moving contact should be removed next The second screw holding the moving contact assem bly should then be ...

Page 7: ... e g COV 8 20 times tap value and measure the operating time Adjust the proper plug until the operating time corresponds to the value in Table 1 Withdraw ing the left hand plug front view increases the operating time and withdrawing the right hand plug front view decreases the time In adjusting the plugs one plug should be screwed in com pletely and the other plug run in or out until the proper op...

Page 8: ...ing position is fixed and cannot be adjusted B The contact gap adjustment for the directional unit is made as follows With the moving contact in the normally closed position i e against the left stop on bridge screw in the stationary contact until both con tacts just close as indicated by a neon lamp in the contact circuit Then screw the stationary contact in toward the moving contact an addi tion...

Page 9: ... 4 37 20 6 20 7 21 0 21 4 23 2 24 9 26 2 103 106 114 122 147 168 180 270 288 325 360 462 548 630 2 6 2 2 5 3 3 5 4 5 6 8 0 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 67 66 64 63 62 59 57 3 88 3 90 3 93 4 09 4 12 4 20 4 38 21 0 21 6 22 1 23 1 23 5 24 8 26 5 110 118 126 136 144 162 183 308 342 381 417 448 540 624 4 12 4 5 6 7 8 10 12 16 0 18 8 19 3 20 8 22 5 25 0 28 0 460 460 460 460 46...

Page 10: ...4 5 6 8 8 8 9 7 10 4 11 2 12 5 13 7 230 230 230 230 230 230 230 66 63 63 63 61 59 58 4 06 4 07 4 14 4 09 4 34 4 40 4 62 21 3 21 8 22 5 23 1 23 8 25 2 27 111 120 129 136 149 163 183 306 342 366 417 448 530 624 4 12 4 5 6 7 8 10 12 16 18 8 19 3 20 8 22 5 25 28 460 460 460 460 460 460 460 64 61 60 58 55 51 46 4 24 4 30 4 62 4 69 4 80 5 20 5 40 22 8 24 2 25 9 27 3 29 8 33 37 5 129 149 168 187 211 260 ...

Page 11: ...nuous Rating Amperes One Second Rating Amperes Power Factor Angle Ø VOLT AMPERES At Tap Value Current At 3 Times Tap Value Current At 10 Times Tap Value Current At 20 Times Tap Value Current 0 5 2 5 0 5 0 6 0 8 1 0 1 5 2 0 2 5 1 7 1 9 2 2 2 5 3 0 3 5 3 8 88 88 88 88 88 88 88 36 34 30 27 22 17 16 0 72 0 75 0 81 0 89 1 13 1 30 1 48 6 54 6 80 7 46 8 30 10 04 11 95 13 95 71 8 75 0 84 0 93 1 115 5 136 ...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...41 116 1A 21 Figure 11 Outline and Drilling Plan for the Type COV Relay in Type FT21 Case 3519A66 Sub 4 ...

Reviews: