Ringers
The NX400 does not contain ringers. However, the QS841A has the capability of managing eight ringer
chassis in a system. The ringer states and output VA would be available when ringers are present in the
system.
Enable
-
Disable Info
This section of the menu displays the enable/disable status of some of the QS841A features. These
values are set by factory default but can be individually configured in the field.
Temp Comp
Temperature compensation
Low Temp Comp
Low temperature compensation
Recharge Ilim
Recharge current limit
Emrgncy Pwr Off
Emergency Power Off (Remote Emergency Battery Disconnect). Enabled
when contact closure is applied to the EPO inputs.
Alarm Test
Form
-
C Alarm Test Feature
Auto Boost
Automatic boost charge
Auto Batt Test
Automatic battery test
Rect Redund
Rectifier redundancy
Mid
-
Cell V Mon
Mid
-
cell voltage monitoring
Imminent Shutdn
Imminent system shutdown alarm (LVBD)
Disconnects
LVBD (Low Voltage Battery Disconnect) and LVLD1
-
3 (Low Voltage
Load Disconnects)
Ringer DC Offset
Ability to reference the output of the ringer to a DC offset
Ringer Redund
Ringer Redundancy Alarm feature
Remote Rect Off
Remote Rectifier Off – Individual Remote Rectifier Standby
Local Write
Whether or not the system can be configured through the local port.
Modem Write
Whether or not the system can be configured through the modem port.
Network Write
Whether or not the system can be configured through the network.
Usernames
Whether or not usernames and password identification has been enabled
Network Settings
This section of the menu displays the settings of the Network parameters for up to two Ports. The
standard QS841A port is considered Port 1. A second network port is achieved by using a Gateway card
communication through a serial port. If two ports are present Port 1(from the QS841A) is the Craft port
and Port 2 from the Gateway would be the LAN port.
Host Name
Network name assigned and configured for the QS841A since it acts as a re pository for data
and services such as e
-
mail, FTP, HTTP, etc that are accessed remotely by other equipment or
users on the network.
IP Address
Internet Protocol address assigned to the QS841A that identifies the unit on the network. The
format for the IP address field is a 32
-
bit numeric address written as four numbers separated
by periods (ddd.ddd.ddd.ddd). Each number digit, d, can be zero to 255. When in the server
mode, a user shall use 192.168.2.1 to access the controller through the craft port.
Subnet Mask
Internal network address assigned for identifying an internal network mask that the QS841A
has been assigned to by a network administrator. The mask selectively includes or excludes
certain equipment on a Host. The format for the Subnet Mask field is a 32
-
bit numeric address
written as four numbers separated by periods (ddd.ddd.ddd.ddd). Each number digit, d, can
be zero to 255.
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...