Page 148
© Copyright 2021 ABB. All rights reserved.
Controller
LED
(Note 3)
User Interface
Display
Rectifier LEDs
(Note 4)
AC DC
ALM
Ringer
LED
Distribution
Module
Board LED
Possible Problem(s)
Possible Solution(s)
RED
MIN, Rectifier
Fail MAJ,
Multiple
Rectifier Fail
MAJ, Battery
on Discharge
Multiple rectifier
thermal alarm:
Excessive ambient
temperature Multiple
rectifier failure
1.
Verify that there is no
obstruction of the vertical
air flow path.
2.
Reset rectifies by removing
them, waiting
approximately 30s and
replacing them.
3.
If problem persists, replace
the rectifiers.
4.
If problem still persists, call
your local field
representative.
RED
MAJ, High
Voltage
High output voltage
from rectifier(s)
Rectifier(s) high
voltage shutdown
Internal rectifier(s)
failure
1.
Reset the rectifier(s) by
removing the rectifier(s),
waiting approximately 30s
and replacing the rectifier
(s).
2.
If problem persists, replace
the rectifier.
3.
If problem still persists, call
your local field
representative.
RED
MAJ, Major
Communicatio
n Fail
-
R
-
(or missing
LVD Board)
LVD Board lost
communication with
the controller.
1.
Replace Distribution
Module Board. (Note 2)
2.
If problem persists, call
your local field
representative.
RED
MAJ, Major
Communicatio
n Fail Minor
Ringer
Redundancy
o (or
missing
Ringer)
No Ringers installed in
a Ringer Chassis.
Ringers not fully
seated in Ringer
Chassis.
1.
Fully seat Ringers in Ringer
Chassis.
2.
Install Ringers in Ringer
Chassis.
3.
If problem persists, call
your local field
representative.
AMBER
MIN, AC Fail
Single Rectifier not
receiving ac power.
•
AC input circuit
breaker has opened.
•
AC input voltage is
out of range.
1.
Verify ac power to rectifier
is available.
2.
Verify rectifier input circuit
breaker is closed.
3.
If problem not corrected,
replace rectifier.
AMBER
MIN, Rectifier
Fail (Note 1)
Rectifier output has
dropped below 36V,
rectifier has entered
hiccup mode.
Replace rectifier.
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...