Page 157
© Copyright 2021 ABB. All rights reserved.
Site ID:
If desired, you may type in a maximum 15 alpha
-
numeric character set to uniquely define a site
location.
Update Serial Link:
Running this command allows the system controller to retake inventory of using
equipment. Use this command to update acknowledged equipment when, for example, a system is to
run with one less rectifier.
Power System
Related Commands
obj,attr
description
sta
cha
ope
type
range of values
ps1,des
Power system description
x
text
“
QS840A
”
ps1,sid
Site ID
x
x
text
Up to 15 characters:
””
ps1,swv
Software version
x
text
ACU software version
ps1,ltt
Lamp test
x
number
1: do lamp test
ps1,usl
Update serial link
x
number
1:perform update serial link
ps1,amt
System ambient temperature
x
number
dd°C
ps1,ptt
Communication port type
x
x
text
“
LOCAL
”,
“
MODEM
”
ps1,dls
Daylight savings time enable
x
x
number
0: disable, 1: enable
ps1,tim
Time
x
x
time
hh:mm:ss (24
-
hour format)
ps1,dat
Date
x
x
date
dd
-
mm
-
yy
DC Plant
Related Commands
obj,attr
description
sta
cha
ope
type
range of values
dc1,stt
Plant state
x
x
text
“
FLOAT
”,
“
BOOST
”
dc1,vdc
Plant voltage
x
number
dd.dd V
dc1,adc
External Battery Shunt Size
x
number
ddd.d A
dc1,sha1
Plant shunt size
x
x
number
0
-
9999:
200
, 0: none
dc1,trd
Plant total rectifier drain
x
number
ddd.d A
dc1,isd
Imminent shutdown enable
x
x
number
0: disable
, 1: enable
dc1,cap
Total rectifier capacity
x
number
ddd.dA
dc1,rss
Rectifier restart
x
x
number
0:no action 1:restart
dc1,bod
Battery on discharge
x
number
0:on discharge, 1: not on discharge
Plant State:
The plant is normally in the float
-
charge mode; however, the super
-
user may instruct the
plant to enter the boost
-
charge mode.
Plant Voltage:
The voltage of the plant at the time of querying.
Plant Current:
The current being drawn by the load at the time of querying.
External Battery Shunt Size:
External battery shunt amp rating.
Plant Total Rectifier Drain:
The current being drawn by the battery and load from the plant at the time
of querying.
Imminent Shutdown Enable:
Factory shipped disabled. When enabled, prior to disconnecting of LVD
contactor during battery discharge, the controller will transmit the Imminent Shutdown alarm to the
host indicating batteries will disconnect from the load in 15 seconds. See Imminent Shutdown in
Section 6 for more details on this feature.
Total Rectifier Capacity:
Sum of the rated outputs of installed rectifiers.
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...