Page 163
© Copyright 2021 ABB. All rights reserved.
Highest Battery Temperature:
When requested, will show the hottest temperature monitored by the
VT
-
Probes.
Total Battery Current:
When requested, will display the current being drawn by the battery string. This
is determined by subtracting the load current from the total rectifier output current.
Plant Battery Test:
When initiated, this function lowers the plant voltage to 44V and allows the
batteries to discharge into the load. This may be used to determine the health of the batteries.
Voltage Imbalance Detection Enable:
Activates the Shorted Cell Detection alarm.
Number of Temperatures Present:
When requested, will display the number of QS873A (VT
-
Probes)
that are currently connected to the system.
Number of mid
-
Cell V Present:
When requested, will display the number of ES771A (Remote Voltage
Monitoring Modules) that are currently connected to the system.
Battery Recharge Current Limit:
The maximum current flowing into battery during the recharge period
is adjustable to any value between 5A and 100A, in 1A increments. At least one battery string must be
present to have this function operate.
Battery Reserve Management
Related Commands
obj,attr
description
sta
cha
ope
type
range of values
br1,hbt
Highest battery temperature
x
number
dd °C
br1,adc
Total battery current
x
number
d A (+ for discharge,
-
for
charge)
br1,bts
Plant battery test (lower rect V)
x
x
number
0:stop 1:start
br1,scd
Battery voltage imbalance detection
enable
x
number
0:disable 1:enable
(Automatically enabled
when mid cell V monitor
present)
br1,ntm
Number of temperatures present
x
d
br1,nvm
Number of mid
-
cell V present
x
d
br1,cle
Recharge current limit enable
x
x
number
0:disable 1:enable
br1,clt
Recharge current limit threshold
x
x
number
5
-
100:10
br1,btr
Discharge test results
x
text
“???”
br1,btc
Battery type
x
x
text
ìFLOODEDî, ìVALVE
-
REGî
br1,bte
Auto test enable
x
x
number
0:disable 1:enable
br1,atd
Auto test date
x
x
date
dd
-
mmm
-
yy
br1,ath
Auto test start hour
x
x
number
0
-
23:0
br1,atw
Auto test min hours after BD
x
x
number
0
-
240:0 hours
br1,tin
Auto test interval
x
x
number
1
-
18:12 months
br1,tmd
Test duration
x
x
number
0.1
-
99.9: 4 hours
br1,cev
End cell voltage
x
x
number
1.5
-
2.0:1.85V/cell
br1,btv
Battery test rectifier voltage
x
x
number
42
-
52:42V
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...