Page 68
© Copyright 2021 ABB. All rights reserved.
Figure 5
-
25: Direct Connection to V+ (shown) / V
-
Output Bus
Terminate Load Connections
-
Direct to Bus Connections
The Distribution Module can be connected directly to the unprotected (no fuses or circuit breakers) dc
output bus. Connections are made from the top of the unit. Lug covers are not provided they must be
ordered separately.
Warning:
Cables terminated directly to the DC output bus in Figure 5
-
25 are unfused. Ensure cables
ends are protected before terminating cables.
Step
Action
1.
Terminate 45° lugs (with 1/4
-
inch holes on 5/8
-
inch centers) to bus landings (hot spots) and torque M6
screws to 65 in
-
lbs. (7.3Nm).
2.
Break tabs off back of lug cover (see Figure 5
-
25).
3.
Insert the front post of the lug cover into the mounting hold and snap the tab on the back of the lug
cover into place.
Lug Cover Front Mounting Hole Insert the
Front Post of the lug cover into the mounting
hole and snap the tab on the back of lug cover
into place
Lug Cover
Break tabs out of
lug cover
Front Post
Insulator Bus Cover
V
-
Bus
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...