Shunt Currents:
A maximum of six measured currents from each Distribution Control and Monitoring
module present in the system is displayed.
Disconnect States:
The status of the LVBD (Low Voltage Battery Disconnect) and LVLD1
-
3 (Low Voltage
Load) disconnects are displayed.
“
None
”
is displayed if there are no contactors in the system.
Alarm Thresholds:
Present alarm threshold settings in xx.xV format of the following system alarms:
Installed Capacity
User entered system battery capacity in AH. Automatically entered when using smart Lithium
batteries.
On
-
Line Capacity
Available battery reserve from installed capacity value directly connected to the bus. It is
always the same value configured for installed capacity except for when the smart lithium
batteries are utilized.
Current
Current flowing into or out of the batteries.
Number Of Strings
The total number of battery strings installed in the system.
Highest Temp
Highest battery temperature being measured by the thermal probes.
Temp Probes
Number of installed thermal probes.
Mid
-
Cell Volts
Number of installed Mid
-
cell voltage measurement modules.
Battery Test Result
Shows whether the most recent battery test was completed, and the reserve time.
Next Test
The date of the next automatic battery discharge test. The automatic
discharge test feature must be enabled for this to work.
Live Reserve Time
Present value of battery reserve time calculated by the controller
Float Voltage Alarms
Very High Major, Very High Minor, BD Major and Very Low major
Boost Voltage Alarms
Very High Major and High Minor
High Batt Temp
Highest temperature being measured by the thermal probes
Reserve Low
Low battery reserve time
High Ambient Temp
High ambient temperature
Low Ambient Temp
Low ambient temperature
Ringer Thresholds:
Present status of up to two ringer chassis:
State
Ringer chassis present or not
VA
Output VA of ringer
Primary
Ringer module present in primary position
Secondary
Ringer module present in secondary/redundant position
Enable
-
Disable Info:
Displays the enable/disable status of the following features:
Temp Comp
Temperature compensation
Low Temp Comp
Low temperature compensation
Recharge Ilim
Recharge current limit
Auto Boost
Automatic boost charge
Auto Batt Test
Automatic battery test
Rect Redund
Rectifier redundancy
Mid
-
Cell V Mon
Mid
-
cell voltage monitoring
Imminent Shutdn
Imminent system shutdown alarm (LVBD)
Local Write
Whether or not the system can be configured through the local port.
Modem Write
Whether or not the system can be configured through the modem port.
Summary of Contents for CPS6000
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 36: ...Page 36 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 98: ...Page 98 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 124: ...Page 124 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 146: ...Page 146 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 152: ...Page 152 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 174: ...Page 174 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 188: ...Page 188 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 192: ...Page 192 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 196: ...Page 196 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 198: ...Page 198 Copyright 2021 ABB All rights reserved This page intentionally left blank ...