background image

Type CWC and CWP Directional Ground Relay

41-242.2F

13

The core screw which is adjustable from the top of
the trip unit determines the pickup value. The trip unit
has a nominal ratio of adjustment of 1 to 4 and an
accuracy within the limits of 10%.

The making of the contacts and target indication
should occur at approximately the same instant.
Position the stationary contact for a minimum of 1/32”
wipe. The bridging moving contact should touch both
stationary contacts simultaneously.

Apply sufficient current to operate the IIT. The opera-
tion indicator target should drop freely.

5. Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient d-c
current through the trip circuit to close the contacts of
the ICS. This value of current should not be greater
than the particular ICS tap setting being used. The
operation indicator target should drop freely. The
contact gap should be approximately 0.47" between
the bridging moving contact and the adjustable sta-
tionary contacts. The bridging moving contact should
touch both stationary contacts simultaneously.

7.2

ROUTINE MAINTENANCE

All relays should be inspected and checked periodi-
cally to assure proper operation.

All contacts should be periodically cleaned. A contact
burnisher S#182A836H01 is recommended for this
purpose. The use of abrasive material for cleaning
contacts is not recommended, because of the danger
of embedding small particles in the face of the soft
silver and thus impairing the contact.

8.0

CALIBRATION

Use the following procedure for calibrating the relay if
the relay has been taken apart for repairs or the
adjustments disturbed. This procedure should not be
used until it is apparent that the relay is not in proper
working order. (See “Acceptance Check”).

1. Contact

By turning the time dial, move the moving contacts
until they deflect the stationary contact to a position
where the stationary contact is resting against its
backstop. The index mark located on the movement
frame will coincide with the “O” mask on the time dial
when the stationary contact has moved through
approximately one-half of its normal deflection.

Therefore, with the stationary contact resting against
the backstop, the index mark is offset to the right of
the “O” mark by approximately .020". The placement
of the various time dial positions in line with the index
mark will give operating times as shown on the
respective time-current curves. For double trip
relays, the follow on the stationary contacts should
be approximately 1/32”.

2. Minimum Trip Current

Type CWC Relay - Connect the upper and lower pole
coils in series and pass current in polarity on both
coils. With one tap screw in the 1 multiplier position
and the other screw in the .25 product tap for the .25-
4 product range or the 2.25 product tap for the 2.25 -
36 product range, apply current and adjust the spring
tension so that the contacts just close at tap value
product.

Type CWP Relay - Connect the relay per Fig. 16. Set
in the lowest tap, apply 100 volts across terminals 6
and 7, and apply minimum pickup current, leading
the voltage by 300 °, (0.20 amperes for the 20-150
range, 0.75 amperes for the 75-600 range.) Then,
adjust the spring tension so that the contacts just
close.

3. Time Curve Calibration

Type CWC relay - Set the time dial to position 6 and
the product tap to .25 or 2.25. Set the multiplier tap to
1. Connect the upper and lower pole coils in series
and pass a current equal to 4 x v tap product in polar-
ity thru the coils. Adjust the permanent magnet
keeper until the operating time is between .95 and
1.01 seconds. Other points on the time curve of Fig-
ure 9 should be within ± 7% of the values shown.
(The multiples of tap product shown in Figure 9 equal
the square of the current passed thru the coils
divided by the tap product.)

Type CWP Relay

 - Connect the relay per the test cir-

cuit of Fig. 16. Set the 6 time dial and the lowest tap.
Apply 100 volts to potential coil and 10 times tap cur-
rent. (Current leading voltage by 300°). relay operate
between 1.43 and 1.51 seconds. Other points of the
time curve should be within ±7% of the value shown
on Fig. 11.

4. Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient d-c
current through the trip circuit to close the contacts of
the ICS. This value of current should not be greater
than the particular ICS tap setting being used. The
operation indicator target should drop freely.

Summary of Contents for CWC

Page 1: ...nk neutral is not available the type CWP relay is applicable 2 0 CONSTRUCTION The type CWC and CWP relays consists of an oper ating unit an indicating contactor switch and optional indicating instantaneous trip unit In addition to the above components the type CWP relay has a phase shifter network The principal component parts of the relay and their locations are shown in Fig 1 8 2 1 OPERATING UNI...

Page 2: ...41 242 2F Type CWC and CWP Directional Ground Relay 2 ...

Page 3: ...Type CWC and CWP Directional Ground Relay 41 242 2F 3 ...

Page 4: ...ottom of the cover A core screw accessible from the top of the switch provides the adjustable pickup range The minimum and maximum pickup points are indicated on the scale which is located to the rear of the core screw 3 0 OPERATION AND CHARACTERISTICS The operating torque for the CWC relay is obtained by energizing the lower pole coil with residual current usually obtained from the line current t...

Page 5: ... 60 Hertz time product curves for the type CWP relay are shown in Fig 11 These curves are taken at maximum torque which occurs with the cur rent lagging the voltage 60 For currents not lag ging by this angle the relay tripping time may be obtained by determining the operating time corre sponding to the product p P Cos 60 6 where P is the actual relay V A product and a is the angle the current lags...

Page 6: ...25 or 250 volt d c type WL relay switch or equiva lent use the 0 2 ampere tap for 48 volt d c applica tions set relay in 2 tap and use S 304C209GO1 Type WL Relay or equivalent 4 4 INDICATING INSTANTANEOUS TRIP IIT Since the minimum and maximum markings on the scale only indicate the working range of the core screw the core screw must be adjusted to the value of the pickup current desired The namep...

Page 7: ...Type CWC and CWP Directional Ground Relay 41 242 2F 7 ...

Page 8: ...41 242 2F Type CWC and CWP Directional Ground Relay 8 ...

Page 9: ...ng time interval It includes the circuit breaker operating time plus a factor allowing for dif ference between actual fault currents and calculated values differences in individual relay performance etc For 8 cycle breakers the value of 4 second is commonly used while for 30 cycle breakers 75 sec ond is used As an example a type CWC relay is to be connected at Station A and set to protect the line...

Page 10: ...me lever in Column 14 is a matter of trial and error The breakers on this system have 8 cycle operating time so that the coordinating time interval should be about 4 second The tap should be chosen so that the relay times for the close in fault and remote fault product values will differ by about the coordinating time interval or 4 second in this case Practically this can be accomplished by severa...

Page 11: ...relays In the example the coordinating time interval was 0 4 second Therefore for fault 2 the relay at D should not operate before the relay at F plus the coordinating time interval In other words the operating time of D should not be less than 0 13 second plus 0 4 0 53 second Similarly the time of the relay at breaker H should not be greater than 0 13 second in order to select with relay F for fa...

Page 12: ...ct the stationary contact to a position where the stationary contact is resting against its backstop The index mask located on the movement frame will coincide with the O mark on the time dial when the stationary contact has moved through approximately one half of its normal deflection Therefore with the stationary contact resting against the backstop the index mark is offset to the right of the O...

Page 13: ...alf of its normal deflection Therefore with the stationary contact resting against the backstop the index mark is offset to the right of the O mark by approximately 020 The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time current curves For double trip relays the follow on the stationary contacts should be approximat...

Page 14: ...red The nameplate data will furnish the actual current range that may be obtained from the ITT unit 9 0 RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be fur nished to the customers who are equipped for doing repair work When ordering parts always give the complete nameplate data 10 0 ENERGY REQUIREMENTS ...

Page 15: ...Type CWC and CWP Directional Ground Relay 41 242 2F 15 THIS PAGE RESERVED FOR NOTES ...

Page 16: ...ed in U S A ABB Automation Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 41 242 2F Type CWC and CWP Directional Ground Relay visit our website at www abbus com papd ...

Reviews: