– InstructIons for InstallatIon, servIce and maIntenance
18
8.6. Auxiliary connections
The auxiliary contacts (19) are connected by 1 mm
2
crimped cables to terminals (17) and are fastened by
M2.5 screws. The following can be used for wiring
each block of auxiliary contacts (1 NO + 1 NC):
•
four cables (x): two for the open contact and two
for the closed contact
•
or three cables and a bridge, as reverser.
The actuator is connected to terminals (x) by a
crimped cable of at least 2.5 mm
2
and is fastened by
M4 screws. The actuator functions correctly
regardless of the polarity of its power supply. The
section of the supply cables must be chosen to suit
the power consumption during the circuit breaker
closing operation and the voltage drop this causes
must not be excessive (see 7.5 - Circuit breaker
commands).
1 Remove the four screws (15) and extract the auxiliary contact box (16)
2 Crimp terminals (17) over cables (18)
3 Connect terminals to contact connections (19), as shown on circuit
diagram
4 Connect cables (18) on both sides
5 Fit box (16) back into circuit breaker
6 Tighten the four screws (15)
7 Connect terminals (17) to terminal box
—
8. Putting into service