3 Installation
3.1 Panel size
In Table 1 are indicated dimensions and weights
of the compartments in the various types of
substation.
Leave enough space, on the front and back, of the
electric panel (fig 3.1) in order to allow the insertion
of the switch (or rectifier) in the cell and the
extraction for inspection and maintenance.
Must be provided enough space even in the back
of the panel, necessary for the opening of the
doors and maintenance operations.
In case of need, the panels are delivered with rear
doors completely screwed. In this case it is possible
to minimize the free space in the back, leaving
a corridor of escape.
8
DCGear
P R O D U C T M A N U A L
Table 1 – Dimensions and weights
Height (H)
Width (W)
Depth (D)
Installation and operation space R1
Installation and operation space R2
Weight
Protection degree (IEC 60529)
Low voltage conpartment
Enclosure
Panal with open dors
mm
mm
mm
mm
mm
kg
-
-
-
Return panel with
disconnector
2105
600
1600
800
N/A
...500
IP4X
IP2X
IP2X
Incoming/feeder
with HSCB
2105
600
1600
800
1250
...600
IP4X
IP2X
IP2X
—
Fig.3.1 – Sizes and
clearances
—
Fig.3.1