DCS500 Pin and Parameter list
A 96
TEST_REF_SEL
Signal of MAINTENANCE function.
Test reference selection. In manual tuning the reference is selected with the signal
TEST_REF_SEL:
0 = ZERO
reference is zero
1 = POT1
reference is POT1_VALUE, 1204
2 = POT2
reference is POT2_VALUE, 1205
3 = SQRW
reference is SQUARE_WAVE, 11206
4 = TEST
reference is TEST_REF, 11207.
11209
S: E2
SC: -
HL: 4
LL: 0
D: 0
U: -
FEXC1_CODE
Signal of MAINTENANCE function.
Type code from field exciter no. 1
0000...0307
FEX-2, half-controlled, single
0308...0819
FEX-31, full-controlled, double
0820...1023
FEX-32, half-controlled, single
10000
DCF501, DCF501B, DCF502B
11210
S: I2
SC: -
HL: -
LL: -
D: -
U: -
FEXC1_COM_STATUS
Signal of MAINTENANCE function.
Communication link timeout-status for field exciter no. 1.
FEXC1_COM_STATUS = 0 = no time-out indication:
B0
timeout when write parameter, no echo for address
B1
timeout when write parameter, no values received
B2
timeout when read parameter, no echo for address
B3
timeout when read parameter, no values received
B4
timeout when read actual values, no values received.
11211
S: PB
SC: -
HL: -
LL: -
D: -
U: -
FEXC1_COM_ERRORS
Signal of MAINTENANCE function.
Number of transmission errors in FEXC-communication link for field exciter no. 1.
11212
S: I2
SC: -
HL: -
LL: -
D: -
U: -
FEXC2_CODE
Signal of MAINTENANCE function.
Type code from field exciter no. 2
0308...0819
FEX-31, full-controlled, double
0820...1023
FEX-32, half-controlled, single
10000
DCF501, DCF501B, DCF502B
11213
S: I2
SC: -
HL: -
LL: -
D: -
U: -
FEXC2_COM_STATUS
Signal of MAINTENANCE function.
Communication link timeout-status for field exciter no. 2.
FEXC2_COM_STATUS = 0 = no time-out indication:
B0
timeout when write parameter, no echo for address
B1
timeout when write parameter, no values received
B2
timeout when read parameter, no echo for address
B3
timeout when read parameter, no values received
B4
timeout when read actual values, no values received.
11214
S: PB
SC: -
HL: -
LL: -
D: -
U: -