DCS500 Pin and Parameter list
A 101
Group 116: MOTOR 2 PROTECTION
MOT2_MEAS_TEMP
Signal of MOTOR_2_PROTECTION- function block.
( S9/16 )
Measured temperature of motor 2.
The unit of the value depends on the selection of AI_CONV_MODE (107, 110):
0 = not selected
1, 2 = value scaled by AI_HIGH_VALUE (108,111) and AI_LOW_VALUE (109,112)
3..5 = unit = degrees
6, 7 = resistance value is ohms
(but displayed in °C )
11601
FB_O: I2
SC: -
HL: -
LL: -
D: -
U: C
MOT2_CALC_TEMP
Signal of MOTOR_2_PROTECTION- function block.
( S9/16 )
Output from thermal model for motor 2.
11602
FB_O: I2
SC: -
HL: -
LL: -
D: -
U: %
Summary of Contents for DCS 500B
Page 8: ......
Page 102: ...Functional Software description 94 DCS 500 Software Description ...
Page 227: ......