Chapter 4 - Signals and Troubleshooting
DCS 600
Operating Instructions
IV F
4 - 13
Code
seven
segm.
display
Text on
LCD of control panel
CDP 312
(or DRIVES WINDOW)
Definition /
Possible source
Signal
number
(ALARM_WORD_1/2)
Remark
A 115
15 CURR RIPP
Armature current ripple
One or several thyristors carry no current.
Check: - Current feedback with oscilloscope
(6 pulses within one cycle visible?);
- Branch fuses, thyristor gate con-
nection and gate-cathode resis-
tance;
- See also parameters
[P 43.10]
,
[P 43.11]
,
and
[P 43.12]
9.05
bit 0
A 118
18 MAIN UVLT
Alarm: Mains Undervoltage (AC)
Setting of undervoltage monitoring with Pa-
rameter
[P 40.01]
or/and
[P 40.02]
Check: - See also Fault Code
F 29
.
9.04 bit 10
A 120
20 CURR DEV
Alarm: Armature Current Deviation
If the current reference ARM_CUR_REF
[P 3.12]
deviates from the current feedback
for more than 5 sec by more than 20 %,
referenced to the rated current, this signal
will be shown.
Check: - Ratio between mains supply
voltage and EMF
9.04 bit 13
A 123
23 MOT2 TEMP
Alarm: Overtemperature MOTOR 2
Check: - Parameter setting
[P 28.13]
correct?
See also Fault Code
F 6.
9.04
bit 8
A 124
24 MOT2 LOAD
Alarm: Overload
MOTOR 2 (Thermal Model 2)
Check: - Overload of motor
- Parameter setting
[P 28.07]
correct?
9.04
bit 9
A 125
25 NO ACK
Alarm: No Acknowledge DC Break or Dyna-
mic Brake contactor
Check: - Digital inputs
[P 15.18], [P 15.20]
9.04
bit 2
RUN =
blocked
A 126
26 CONV FAN
Alarm: No (Thyristor Power) Converter FAN
Acknowledge
Check: - See Fault Code
F 50.
9.04 bit 12