background image

Troubleshooting Guidelines

Condition

Potential Cause

Solution/Action

Push-to-test button will not trip  

circuit breaker.

1. Circuit breaker is OFF.

2. Circuit breaker is tripped.

3. Load center is not energized.

4.  The DFCI neutral (pigtail) is not 

connected to the neutral bus bar.

5. Circuit breaker is damaged.

1. Turn circuit breaker ON.

2.  Reset the breaker by switching it OFF 

and then ON.

3.  Check to be sure load center is 

energized.

4. Check neutral (pigtail) connection.

5. Replace circuit breaker.

Circuit breaker trips (handle in 

center position and trip flag 

appears).

1.  Circuit breaker is not installed 

correctly.

2.  An overload condition exists on the 

branch circuit (total current drawn 

exceeds rating of breaker).

3.  An arc or ground fault condition 

exists on the branch circuit, or circuit 

breaker is damaged.

4.  A load or combination of loads on the 

branch circuit emits a current 

signature that looks like an arc fault.

1.  See installation instructions on  

1st page.

2.  Assess the current on the circuit drawn 

by all the loads by summing all branch 

amperages (divide the rated wattage of 

each load by 120). If this total is greater 

than the circuit breaker rating, the 

circuit is overloaded and some of the 

load should be removed.

3.  Test for arc and ground faults by 

completing instructions below.

4.  Contact ABB (see contact information 

below) for troubleshooting 

information.

After the tripped breaker is reset,  

LED is ORANGE then turns RED.

The breaker detected a ground fault 

from the push-to-test or from the load 

circuit and tripped.

If the trip occurred without pressing the 

push-to-test button, then the leakage to 

ground must be cleared for proper 

operation of the ground fault detection.

After the tripped breaker is reset,  

LED is ORANGE then turns 

YELLOW.

The breaker detected an arc fault from 

the push-to-test or from the load circuit 

and tripped.

If the trip occurred without pressing the 

push-to-test button, the arc fault must be 

cleared for proper operation of the arc 

fault detection.

After resetting the breaker, the 

breaker trips immediately.

This condition indicates that the DFCI 

has detected a short circuit, ground 

fault or a grounded neutral. If the 

solution/action recommendation does 

not resolve the issue, the breaker may 

have lost its ground fault sensing 

capability due to a sensing circuit 

failure.

1.  Remove the load’s neutral wire from  

the breaker.

2.  Reset the breaker by switching it OFF 

and then ON.

3.  If the breaker does not trip, a short 

circuit, ground fault or grounded 

neutral must be cleared from the 

downstream circuit.

4. If the breaker trips, replace breaker.

The circuit breaker is blinking 

constantly RED and YELLOW after 

push-to-test.

This condition indicates that the DFCI 

lost its ability to detect ground and arc 

faults.

Replace circuit breaker.

To test for arc and ground faults:

Unplug all items from the receptacles in branch circuit. Reset circuit breaker by pushing its handle to the OFF position and 

then to the ON position:

1.  If breaker trips with all loads OFF: Check permanent electrical circuit wiring, arcing, poor insulation, shorted wires, wet 

connections, wet conduit, a neutral lead pinched to a grounded metal box, receptacle leakage, loose connections, or 

other faults that could cause safety features in the breaker to open the circuit.

2.  Switch ON one of the original loads. Reset the breaker. If breaker does not trip with this load ON, switch on an additional 

load. Repeat until breaker trips. Examine last additional load for possible faults.

Loads and/or wiring suspected of having faults should not be restored to service.

NOTICE: These instructions do not cover all details or variations in equipment nor do they provide for every 

possible contingency that may be met in connection with installation, operation, or maintenance. Should further 

information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s 

purposes, the matter should be referred to the ABB Company. See contact information below.

For troubleshooting or service related questions, contact ABB at 800-782-8061  

or at epis.component.support@abb.com

DEH41820  9/19

ABB Inc.

305 Gregson Drive

Cary, NC 27511

electrification.us.abb.com

© Copyright 2019 ABB. All rights reserved
Information provided is subject to change without notice. Please verify all details with ABB. All values are design or typical
values when measured under laboratory conditions, and ABB makes no warranty or guarantee, express or implied, that
such performance will be obtained under end-use conditions.
GE is a registered trademark used under license from General Electric company.

Summary of Contents for DEH41820

Page 1: ...ee Troubleshooting Guides on the next page on how totroubleshoot a DFCI WARNING Do not reverse feed Do not subject to high voltage or high pot tests Remove the circuit breaker before high potting occurs on the circuit or the system DEH41820 HOMEOWNER INSTALLER INFORMATION Dual Function Circuit Interrupter DFCI Test Procedures DFCI should be tested regularly at least once per month The test feature...

Page 2: ...esolve the issue the breaker may have lost its ground fault sensing capability due to a sensing circuit failure 1 Remove the load s neutral wire from the breaker 2 Reset the breaker by switching it OFF and then ON 3 If the breaker does not trip a short circuit ground fault or grounded neutral must be cleared from the downstream circuit 4 If the breaker trips replace breaker The circuit breaker is ...

Page 3: ...de alto voltaje o de alta potencia Remueva el cortacircuitos antes de que ocurra un evento de alta potencia en el circuito o en el sistema eléctrico DEH41820 INFORMACIÓN PAR A EL PROPIETARIO Y EL INSTAL ADOR Interruptor de Función Doble Procedimientos de prueba El DFCI debe probarse con una frecuencia de al menos una vez por mes La función de prueba del cortacircuitos permite al propietario probar...

Page 4: ...a es posible que el cortacircuitos haya perdido la capacidad de detectar fallas a tierra debido a una falla en el circuito de detección 1 Remueva el cable neutral de la carga del cortacircuitos 2 Restablezca el cortacircuitos moviendo la manija a la posición de apagado OFF y luego moviéndola a la posición de encendido ON 3 Si el cortacircuitos no interrumpe un corto circuito una falla a tierra o u...

Page 5: ...ISSEMENT Ne pas inverser l alimentation Ne pas soumettre à de tests de haute tension ou de haut voltage Enlevez le disjoncteur avant que la haute tension ne se produise dans le circuit ou le système DEH41820 INFORMATIONS POUR LE PROPRIÉTAIRE ET L INSTALL ATEUR Disjoncteur double fonction Dual Function Circuit Interrupter DFCI Procédures de test Les DFCI devraient être régulièrement testés au moins...

Page 6: ...e à cause d une défaillance du circuit de détection 1 Enlevez le fil de charge neutre du disjoncteur 2 Réinitialisez le disjoncteur en le basculant sur OFF puis sur ON 3 Si le disjoncteur ne se déclenche pas il faut débloquer un court circuit un défaut de terre ou un sol neutre du circuit en aval 4 Si le disjoncteur se déclenche remplacez le disjoncteur Le disjoncteur clignote constamment ROUGE et...

Reviews: