ABB i-bus
®
EIB
Appendix
© 2006 ABB STOTZ-KONTAKT GmbH
98
A.5 Feedback
status
behaviour
The following table provides a simple overview of when feedback objects are
sent. They depend on the state of the output and the received command.
With the “Switch/Status” object, it is also possible to set whether
transmission is continuously on or only after a change.
“–” means that the feedback object is not sent.
Switch object “Switch/Status”
Switch feedback content
Old state
Received
command
New state
“always
send”
“send on
change”
OFF
OFF command
OFF OFF -
OFF
DIM command
OFF OFF -
OFF
VALUE command
OFF OFF -
OFF
Scene command
OFF OFF -
OFF
OFF command
ON ON ON
OFF
DIM command
ON ON ON
OFF
VALUE command
ON ON ON
OFF
Scene command
ON ON ON
ON
OFF command
ON ON -
ON
DIM command
ON ON -
ON
VALUE command
ON ON -
ON
Scene command
ON ON -
ON
OFF command
OFF OFF OFF
ON
DIM command
Min. Dimm
ON
-
ON
VALUE command
OFF OFF OFF
ON
Scene command
OFF OFF OFF
Switch object “Brightness value/Status”
Switch feedback content
Old state
Received
command
New state
“always
send”
“send on
change”
OFF
OFF command
OFF OFF -
OFF
DIM command
OFF OFF -
OFF
VALUE command
OFF OFF -
OFF
Scene command
OFF OFF -
OFF
OFF command
ON / y%
y %
y %
OFF
DIM command
ON / y%
y %
y %
OFF
VALUE command
ON / y%
y %
y %
OFF
Scene command
ON / y%
y %
y %
ON / x%
OFF command
ON / x%
x%
-
ON / x%
DIM command
ON / x%
x%
-
ON / x%
VALUE command
ON / x%
x%
-
ON / x%
Scene command
ON / x%
x%
-
ON / x%
OFF command
ON / y%
y %
y %
ON / x%
DIM command
ON / y%
y %
y %
ON / x%
VALUE command
ON / y%
y %
y %
ON / x%
Scene command
ON / y%
y %
y %
ON
OFF command
OFF 0%
0%
ON
DIM command
Min. Dim
Min. Dim %
Min. Dim %
ON
VALUE command
OFF 0%
0%
ON
Scene command
OFF 0%