Device
technology
© 2006 ABB STOTZ-KONTAKT GmbH
11
ABB i-bus
®
EIB / KNX
Isolation category
- Overvoltage category
- Pollution degree
III to DIN EN 60 664-1
2 to DIN EN 60 664-1
EIB / KNX safety extra-low voltage
- SELV 24 V DC
DALI voltage
- typical 16 V DC (9.5…22.5 V DC)
to DIN IEC 60929 / 62386
Temperature range
- Operation
-5° C ... + 45° C
- Storage
-25°C...+ 55°C
- Transport
-25°C...+ 70°C
Design
- Modular installation device (MDRC)
Modular installation device, pro
M
- Dimensions
90 x 72 x 64,5 mm (H x W x D)
- Module width
4 modules at 18 mm
- Mounting depth
68 mm
Installation
- On 35 mm mounting rail
to DIN EN 60 715
Mounting position
- As required
Weight
- 0.190 kg
Housing, colour
- Plastic housing, grey
Approvals
- EIB / KNX to EN 50 090-1, -2
Certification
CE mark
- in accordance with the EMC guideline and low
voltage guideline
Table 2 b
DALI-Gateway DG/S 1.1, Technical data
Note:
The DALI-Gateway conforms to the SELV properties in accordance with DIN EN 410. DALI does not require
SELV properties, and it is possible to route the DALI control lines together with the mains voltage on a multi-core
cable.
Connection of 230 V mains voltage to one of the DALI outputs leads to the destruction of the DALI end stage and
the output.
User programs
Device designation
Application program
Max. number of
communication objects
Max. number of group
addresses
Max. number of
associations
DG/S 1.1
Dim Lightscenes Dynamic 1f/1
251 254
254
Table 3
Application programs for DG/S 1.1
Note:
The programming requires EIB Software Tool ETS2 V1.3 or higher. If ETS3 is used, a “.VD3” type file must be
imported.
The user program is located in ETS2 / ETS3 under ABB/Beleuchtung/ DALI/ Dim Lightscenes Dynamic 1f/1.