Commissioning
The parameterisation of the gateway and the DALI equipment is
implemented with the user program
"Dim Lightscenes Dynamic 1f/1"
and the
ETS program (from version ETS2V1.3). If ETS3 is used, a “.VD3” type file
must be imported. The following work must be carried out:
- Assignment of the physical EIB / KNX device addresses
- Optional readdressing of the DALI device (see section 3)
- Parameterisation of the gateway properties
- Assignment of the communication objects to EIB / KNX groups
A PC or laptop with ETS is required for parameterisation. A connection to
the ABB i-bus
®
can be implemented via an RS232 or USB interface.
The DALI-Gateway allocates an address to every connected DALI device
which does not have a DALI address and makes it available on the
EIB / KNX. An individual, project-related readdressing is also possible
without the ETS software tool.
The installation and commissioning may only be carried out by
electrical specialists. The appropriate norms, guidelines,
regulations and specifications should be observed when
planning and setting up electrical installations.
2.6
Assignment of the physical
EIB / KNX address
The assignment of the physical EIB / KNX address of the DALI-Gateway
DG/S 1.1 is carried out via the ETS and the programming button on the
device.
The DALI-Gateway DG/S 1.1 has a programming button for assigning the
EIB / KNX physical address which is located on the collar of the device. The
red programming LED lights up after the button has been pushed. It
switches off as soon as ETS has assigned the physical address or the
programming button is pressed again.
2.7
Display elements
Green LED: Lights up green if the voltage supply is present and the device
is ready for operation with the DALI devices.
The green LED switches off if the voltage supply fails and DALI
voltage is no longer generated. The DG/S 1.1 is still
programmable via the EIB / KNX.
Yellow LED:
Normal operation
Lights up yellow in the event of a DALI fault.
A DALI fault is a DALI short circuit or a ballast or lamp fault.
Test operation
Flashes yellow slowly (1 Hz) in test mode.
Initialisation
Flashes yellow rapidly (10 Hz) during initialisation.
The initialisation phase starts after download, EIB
/
KNX
voltage recovery, after test mode or after the elimination of a
DALI short circuit. The initialisation phase may take up to 90
seconds depending on the number of DALI devices. If more
than 64 DALI devices are connected to a channel, the device
will not exit the initialisation phase. The yellow LED will
flash continuously.
Red LED:
Lights up red if the device is in the EIB programming mode.